Where raceways or cables enter above the level of uninsulated live parts of cabinets, cutout boxes, and meter socket enclosures in a wet location, a(an) _____ shall be used.
fitting listed for wet locations
312.2
Nonmetallic-sheathed cable shall be permitted to be unsupported where the cable is _____.
fished between access points through concealed spaces in finished buildings or structures
334.30(B)(1) and (2)
Type UF cable and associated fittings shall be _____.
listed
340.6
Where a PVC conduit enters a box, fitting, or other enclosure, a bushing or adapter shall be provided to protect the wire from abrasion unless the box, fitting, or enclosure design provides equivalent protection. True or false?
True
352.46
Power distribution blocks installed in metal wireways on the line side of the service equipment shall be marked "suitable for use on the line side of service equipment" or equivalent. True or False?
True
376.56(B)(1)
When counting the number of conductors in a box, a conductor running through the box with an unbroken loop or coil not less than twice the minimum length required for free conductors shall be counted as _____ conductor(s).
two
314.16(B)(1)
Bends made in interlocked or corrugated sheath Type MC cable shall have a radius of at least _____ times the external diameter of the metallic sheath.
seven
330.24(B)
Type RMC conduit shall be permitted to be installed where subject to severe physical damage. True or False?
344.10(E)
Liquidtight flexible metal conduit shall be securely fastened within _____ of each box, cabinet, or other conduit termination.
12 in
350.30(A)
For raceways terminating at a cable tray, a(an) _____ cable tray clamp or adapter shall be used to securely fasten the raceway to the cable tray system.
listed
392.18(G)
The ampacities specified in Table 310.16 are based on _____.
conductors rated 60°C, 75°C, or 90°C, an ambient temperature of 86°F, no more than three current-carrying conductors
310.16(2), (3), and (4)
Type AC cable outer armor is permitted to act as an equipment grounding conductor. True or False?
True
320.108
Threadless couplings and connectors used with intermediate metal conduit shall be made _____.
tight
342.42(A)
When LFMC is used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or for equipment requiring movement after installation, a(an) _____ conductor shall be installed.
equipment grounding
350.60.
When a building is supplied with a(an) _____ fire sprinkler system, ENT shall be permitted to be used within walls, floors, and ceilings, exposed or concealed, in buildings exceeding three floors above grade.
NFPA 13
362.10(2) Ex
Where there are no adjustment or correction factors required, the service conductors for a rated service of _____ supplying the entire load associated with an individual dwelling unit, may be sized applying Table 310.12.
100A, 200A, 400A
310.12(A)
The radius of the curve of the inner edge of any bend during or after installation of Type NM cable, shall not be less than _____ times the diameter of the cable.
5
334.24
FMC shall not be installed _____.
in wet locations, embedded in poured concrete, where subject to physical damage
348.12(1), (6), and (7)
Galvanized steel and stainless steel EMT, elbows, couplings, and fittings can be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where _____.
protected by corrosion protection
358.10(B)(1)
A multioutlet assembly shall not be installed _____.
in hoistways, where subject to severe physical damage, where subject to corrosive vapors
380.12(2), (4), and (5)
The total volume occupied by two internal cable clamps, six 12 AWG conductors, and a single-pole switch is _____ cu in.
20.25
314.16(A), Table 314.16(B), and 314.16(B)(1) through (4)
Armored cable shall not be installed _____.
in damp or wet locations, where subject to physical damage, where exposed to corrosive conditions
320.12(1), (2), and (4)
The minimum radius of a field bend on trade size 1 1/4 RMC is _____ in.
8
344.24 and Chapter 9, Table 2
Liquidtight nonmetallic flexible conduit is not permitted to be used where _____.
subject to physical damage, ambient temperatures exceed its listing, in lengths greater than 6 ft unless approved
356.12(1), (2), and (3)
The voltage between conductors in a surface metal raceway shall not exceed _____ unless the metal has a thickness of not less than 0.040 in. nominal.
300V
386.12(2)