NFPA 72 Basics
Initiating & Notification
Installation Rules
Systems & Signals
Codes & Standards
100

Chapter of NFPA 72 that covers inspection, testing, and maintenance.

What is Chapter 14?

100

Example of an alarm initiating device.

What is a manual fire alarm box?

100

Heat detectors on walls must be mounted between __ and __ inches from the ceiling.

What is 4" and 12"?

100

Removing an addressable smoke detector from an SLC causes this signal.

What is trouble?

100

Dwelling unit smoke detectors cannot be installed here.

What is in attics?

200

Minimum temperature fire alarm equipment must be installed above.

What is 32°F?

200

Example of a supervisory initiating device

What is a water level switch?

Valve Tamper and Air Pressure Switches also

200

Class A vertical runs must be separated by at least __.

What is 1 foot?

200

List the priority order: Life safety, Property protection, Trouble with property protection, All other.

What is 1–4 in that order?

200

Fire alarm systems are sometimes integrated with which four other systems? name one

What are burglary, BAS, access control, mass notification?

300

Trouble signals must be indicated within how many seconds of a system fault?

What is 200 seconds?

300

Tactile notification appliances alert by which sense?

What is touch?

300

Outgoing and return conductors of a Class A circuit can share a raceway if distance does not exceed __.

What is 10 feet?

300

Remote supervising stations must transmit __ signals.

What are supervisory and alarm?

300

Which code does NOT require installation of fire alarm systems?

What is UL 268?

400

Chapter of NFPA 72 that provides requirements for documentation.

What is Chapter 7?

400

Evacuation signals must produce the Temporal __ signal.

What is Temporal 3?

400

Smoke detectors on smooth ceilings can be spaced __ apart.

What is 30 feet?

400

Public fire reporting systems transmit which type of signal?

What is alarm?

400

Fire suppression systems most commonly used

What are wet-pipe systems?

500

Requirements for ECS are found in NFPA 72 Chapter __.

What is Chapter 24?

500

Low-frequency alarm signal required for sleeping areas.

What is 520 Hz?

500

Rechargeable power supplies for smoke alarms must recharge in __ or less.

 What is 4 hours?

500

An open circuit on a Class B SLC results in what?

What is loss of devices downstream of the open?

500

Requirements for CO detectors were once in which NFPA?

What is NFPA 720