Transfer Switch
Motor
Generator Theory
Alternator
Watertight
100

What are the utility sensing wires on a generac single phase transfer switch

N1&N2

100

An air cooled unit should run at what rpms

3600

100

When the cold smart start feature is enabled how long will the generator warm up for before the load is applied 

30 seconds 

100

What would be going on with a air cooled unit when you find gray dust in the bottom of the gen by the fan 

Generators brushes need replaced

100

What should you do if you forget to put an item used on your ticket?

Put it on teams in missing parts with customer name and what's missing 

200

What wire grounds itself and transfers the actuator?

Wire 23

200

What is the minimum allowed compression on a standby air cooled generator motor 

150 psi

200

What is the minimum clearance from openings in walls(operable windows,doors,vents window wells,soffets) that a generac generator can be placed 

5ft 

200

What would be the rpm for a 4 pole rotor 

1800

200

What should you do with your ticket when rescheduling a job and who should you let know 

Leave your ticket open and let your scheduler know

300

What wire gives power to wire 23 to allow transfer

Wire 194

300

What is the maximum allowed gas pressure on air cooled units 

11 inw

300

The Evolution generator is operating in auto,utility voltage is avaliable and the transfer switch has switched over to the generator position.  Why is this happening

N1 or N2 fuse is blown (open)

300

What should be the resistance on the slip rings of a rotor 

5-12 ohm

300

What should you write on the top of your ticket when completing a repair under warranty 

*Need to file warranty 

400

What is the proper output voltage on A&B communication wires for kohler units 

4 VDC

400

How do you find top dead center on a 24kw air cooled unit 

Use a long wooden stick and roll engine over until piston is topped out on the compression stroke

400

What is the maximum cooldown for a generac generator?

15 min

400

What's the voltage need for excitation 

Battery voltage 

400

What is the last picture you should take on the generator in watertight?

Controller in auto picture

500

What does transfer wire warning mean?

Controller is not sensing battery voltage on wires194 or 23

500

How many feet does each 90 in a pipe run add for a generac generator, what about a kohler generator 

Generac- 5 ft

Kohler- 8ft

500

The generator controller is in auto the unit is running and the transfer switch has transferred to the standby position if wire 23 is shorted to ground when utility service returns what will happen

Nothing

500

What is all of wire numbers coming from the stator on a generac

1&4 2&3 11s&44s 2&6

500

When on call what must be done before you go out to a call and what do you do if the install is 6 months or less

Collect 295 and no charge if 6 months or less