UFAD/DV
Terminals
GRD
Chilled Beams
Antec
100

This is the ideal location for a ceiling mounted displacement diffuser

What are Transient areas?

100

The component of a terminal  unit which opens and closes to regulate airflow.

What is a damper?

100

This material is typically the most cost effective option for Price Industries GRD products.

What is steel?
100

This type of chilled beam requires airflow through the unit.

What is an ACTIVE chilled beam (or ACB)?

100

Another name to describe the VFX.

What is a high accuracy terminal unit?

200

This is the most cost-effective underfloor solution for perimeter applications

What is LNT?

200

The type of sound that breaks out through the casing of a terminal unit.

What is radiated sound?

200

The required length of straight hard duct upstream of the diffuser, per ASHRAE 70-2006.

What is 3 equivalent duct diameters?

200

This chilled beam unit can provide sensible cooling without supply air.

What is a PASSIVE chilled beam (or PCBL)?

200

When a reheat or cooling coil will operate from 0-100% at the same time airflow is added to the room.

What is synchronous temperature control?

300

This is the parameter by which we size displacement diffusers.

What is 40fpm face velocity?

300

The reheat accessory commonly installed on the discharge of a unit which allows for an instantaneous response to heat.

What is an electric coil?

300

Most diffusers are tested while installed in a ceiling. However, when they are installed without a ceiling, the throw length should be adjusted by this amount.

What is 0.70 (or reduced by 30%)?

300

This is typically induced through an active chilled beam's water coil?

What is Room Air?

300

The most common type of coating used on VV/VFX in corrosive fume hood applications.

What is Phenolic Class 1 coating?

400

This sensor is critical to the success of every underfloor project.

What is a Plenum Pressure Sensor?

400

The pressure provided by the air handler to the inlet of a terminal unit.

What is inlet static pressure?

400

The typical source of dirt embedded in the ceiling, sometimes called "Smudging".

What is poor house keeping?

400

This is recommended for the entering chilled water temperature for non-condensing beam applications.

What is 2-3 degrees above room dew point?

400

This requires a room pressure sensor and some sort of display (i.e. local monitor, front end system, etc.).

What is room pressure monitoring?

500

The Ventilation effectiveness for ceiling heights above 18ft.

What is 1.5?

500

The phenomenon in which a poor inlet condition has a negative impact on airflow measurement, control, sound generation, and pressure drop.

What is "system effect"?

500

This is the rule-of-thumb depth of a ceiling obstruction that will obstruct the path of an air jet from the diffuser.

What is any depth that is equal to or greater than a 10 degree angle from the diffuser?

500

This contributes to energy savings by using a chilled beam system.

What is: Using the water side to call/heat space instead of just air?  Induction through the coil?  Reduction in air, air handler size, fan energy?

500
An accessory that is highly recommended to include when performing direct pressure control, in addition to the room pressure sensor.

What is the door contact switch (DCS)?