Definitions
Ventilation / Exhaust
Ducts
Refrigeration
Misc
100

A pressure-actuated valve held closed by a spring or other means & designed to relieve pressure automatically in excess of the device's settings. 

Pressure Relief Valve

100

Has an exhaust rate capacity of 100CFM intermittent or 25 CFM continuous

Kitchen Exhaust 

100

Design temperature of air to be conveyed in this duct shall be less than 250 degrees. 

Flex Duct

100

Chemical Refrigerant R-744

Carbon Dioxide 

100

Appliances shall not be installed in a location where subject to this unless protected by approved barriers. 

Mechanical Damage

200

A type of boiler furnishing steam at pressures not exceeding 15 psi

Low-Pressure Steam-Heating Boiler

200

These shall not be within 10 feet horizontally from any hazardous or noxious contaminant source (such as vents, streets, alleys, parking lots, and loading docks). 

Intake Openings

200

The use of these boards to form plenums shall be limited to systems where the air temps do not exceed 125 degrees. 

Gypsum Boards

200

Used refrigerants that shall not be reused in a different owner's equipment or appliances unless tested & found to meet the purity requirements of AHRI 700.

Reclaimed Refrigerants

200

Required in every boiler and modular boiler in the supply and return piping. 

Shutoff Valve

300

This class of this liquid have a closed cup flash point at or above 100 degrees and below 140 degrees. 

Class II Combustible Liquid

300
Supply air to this space shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60% or less. 

Swimming Pool

300

These metallic ducts not having an approved protective coating shall be completely encased in not less than 2 inches of concrete. 

Underground ducts

300

Refrigeration systems with this refrigerant shall comply with IIAR 2, IIAR 3, IIAR 4, and IIAR 5. 

Ammonia

300

For protection of the structure, the diameter of these shall not exceed 40% of the stud depth. 

Bored holes in wood studs

400

An air intake device used to capture by entrapment, impingement, adhesion or similar means grease, moisture, heat, and similar contaminants before they enter a duct system

Hood or Kitchen Hood. 

400

This type of dryer's ducts shall have a minimum clearance of 6 inches to combustible material. 

Commerical clothes dryer

400
This coating used on filters shall have a flash point not lower than 325 degrees F. 

Liquid adhesive coating

400

These rooms are not required for listed equipment & appliances containing more than 6.6 pounds of refrigerant, regardless of the refrigerant's safety classification. 

Machinery Room

400

These shall be tested hydrostatically at one and one-half times the maximum system design pressure, but not less than 100psi. 

Hydronic Piping Systems

500

An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors or floors and the roof. 

Shaft

500

Where these specified motors are required, their bearings shall not be within the airstream and all their parts shall be grounded

Spark Resistant fans

500

Smoke detectors shall be installed in these systems with a design capacity greater than 2000 CFM. 

Return Air System

500

A clearly identified switch of the break-glass type or with an approved tamper-resistant cover shall provide off only control of refrigerant compressors, pumps, and normally closed automatic valves located in the machinery room. 

Refrigeration System Emergency Shut Off

500

Where vents pass through insulated assemblies, this will be constructed of no less than No. 26 gauge sheet metal shall be installed to provide clearance between the vent and the insulation material. 

Insulation Shield