EOL value in a Horn Strobe
What is 3.9K
How many Input Zones are on the controller
What is 6
Purpose of a Vesda System
What is sampling the air for pre combustion partials
First 2 steps when called out for service of a suppression system
What is Notify tool owner to put system into bypass mode. 2nd step, removal of actuators
Wire size on the THIS probes
What is 32 AWG
EOL Value in a Manual Release
What is No resistor in Manual Release
How many Outputs on the controller
What is 4
The 4 signal notifications on a Vesda
What is Action, Alarm, Fire 1 and Fire 2
How often is a standard service required on a FSS or FDS system
What is 1 year
If the cutting dyes on your stripers are damaged
What is put into trash and replace the Tool
The cause of a low pressure Fault (E-30)
What is jumper missing from discharge module
What does N.A.C. stand for
What is Notifying Alarm Circuits
Maximum travel time for notification of contaminates
What is 90 seconds
When do batteries need replacement
What is ever 3 years even if still charged
Size of wrench needed on a 3/8th Hex bolt
What is 9/16ths
Reason for a Lock Out Valve
What is prevention of discharge and protection of personnel.
What are the Programable Relays identified as
What is Alarm, Trouble and Supervisory
Relays that the digital gauges are landed to
What is K1, K2, K3, K4
At what percentage is a cylinder weight needed to be refilled
What is any lower then 90%
Size of wrench needed for a 1" compression Fitting
What is 1-1/2"
Contact state in an IR detector
What is Normally Open
Value of resistor used in panel relays
What is 4.7K
Area coverage of a VLF 250 in square footage
What is 2,700 square ft.
When do flex hoses need to be replaced or hydrostatic tested
What is every 5 years
Type of pipe used in an LDS enclosure
What is 1/2" Stainless Schedule 40