NEC section dealing with conduit bodies and fittings
What is Section 314
Minimum length for a straight pull with two 5-inch conduits and entry and exit
What is 40 inches
For an angle pull, the minimum bend radius for non-shielded cable
What is 24 times the cable OD
Ingress Progression
What is the IP classification
100 cubic inches
What is the min area of a junction box where a power distribution block is installed
Type of LB with the most interior volume
What is A MOGAL lb
Minimum distance between entry and exit points for 4" conduits in an angle pull
What is 24"
48 times the OD of the largest conductor
What is the minimum box length for straight pulls of shielded cable
Provides protection against dust, light and indirect splashing but is not intended for outdoor use
What is NEMA 12
NEC Article covering grounding and bonding
What is Article 250
Installed to protect conductors and to provide a grounding connection
What is a grounding bushing
Watertight and corrosion resistant
What is NEMA 4X
36 times the largest cable OD
What is the min box length for shielded cable
NEMA rating for a box that resists dust and water splashing from any direction
What is NEMA 13
Has gasket to prevent water entering from any angle
What is watertight
Minimum box depth for a straight pull with a 5" conduit at both entry and exit points with three #750 kcmil cable installed
What is only deep enough for the lock nut or grounding bushing to be installed
NEC article covering pull and junction box requirements
What is 314, Part III
65 gallons per minute for 5 minutes
What must a NEMA 4 enclosure be able to withstand
NEC section covering the requirements for handholes containing conductors operating at over 1000 volts
What is NEC section 314.71
Type of coupling that can be used to join two RMS conduits that cannot be turned
What is a hinged coupling
Handhole construction standard
What is ANSI / SCTE 77-2013
NEC section covering the required labeling boxes or enclosures
What is section 314.72(E)
Protection against water (IP Classification)
What is the second number in the classification code
#8 in the IP classification code
What is the classification code for suitable for continuous submersion