Fittings and Conduit Bodies
Junction Box (less than 1000v)
Junction Box (greater than 1000v)
NEMA Ratings
Instructors Choice
100

NEC section dealing with conduit bodies and fittings

What is Section 314

100

Minimum length for a straight pull with two 5-inch conduits and entry and exit

What is 40 inches

100

For an angle pull, the minimum bend radius for non-shielded cable

What is 24 times the cable OD

100

what does IP stand for?

Ingress progression

100

which conduit body has cover openings on both sides?

LRL

200

Type of conduit body with the most interior volume

What is A MOGAL 

200

Minimum distance between entry and exit points for 4" conduits in an angle pull 

What is 24"

200

48 times the OD of the largest RACEWAY

What is the minimum box length for straight pulls of shielded cable

200

Provides protection against dust, light and indirect splashing but is not intended for outdoor use  

What is NEMA 12

200

ABBREVIATION FOR AN ENTRANCE ELL FITTING

SLB

300

Installed on connector to protect conductors and to provide a grounding connection

What is a grounding bushing

300

Watertight and corrosion resistant 

What is NEMA 4X

300

36 times the largest RACEWAY

What is the min box length for shielded cable

300

Nema box suitable for a oil refinery

What is NEMA 7

300

Has gasket to prevent water entering from any angle

What is watertight

400

this is a gasketed fitting

myers hub

400

Minimum box depth for a straight pull with a 5" conduit at both entry and exit points with three #750 kcmil cable installed

What is only deep enough for the lock nut or grounding bushing to be installed

400

NEC article covering pull and junction box requirements

What is 314, Part III

400

65 gallons per minute for 5 minutes

What must a NEMA 4 enclosure be able to withstand

400

WHAT DOES THE FIRST NUMBER OF THE IP CLASSIFICATION DESIGNATE?

SOLID OBJECTS

500

Type of coupling that can be used to join two RMS(rigid) conduits that cannot be turned

What is a hinged coupling

500

A STANDARD SQUARE BOX IS AN EXPENSIVE ALTERNATIVE TO WHAT?

type t conduit body

500

NEC section covering the required labeling boxes or enclosures

What is section 314.72(E)

500

this enclosure s suitable for food processing

nema 13

500

what is nema 6 box suitable for?

 suitable for continuous submersion