WHAT IS THE MINIMUM SINGLE STANDARD SIZE OCPD NECESSARY TO PROTECT A BRANCH CIRCUIT SUPPLYING A 13 AMP NON-CONTINOUS LOAD AND AN 18 AMP CONTINOUS LOAD?
40 AMP BREAKER
13 + (18 x 1.25)=35.5
240.6--->40 AMP OCPD
THE OBJECTIVE OF THE IBEW IS TO SEEK A _______ STANDARD OF LIVING.
HIGHER
BETTER
IMPROVED
GENERALLY STOP BUTTONS ARE WIRED IN _____ WITH THE CONTROL CIRCUIT
SERIES
NAME THE PART IN A SINGLE PHASE MOTOR THAT OPENS A CONTACT TO REMOVE THE CAPACITOR(S) AND/OR START WINDING WHEN THE MOTOR REACHES A CERTAIN SPEED.
CENTRIFUGAL SWITCH
WHAT IS THE STANDARD DERATING PERCENTAGE FOR A CALCULATED NEUTRAL LOAD FOR AN OVEN OR DRYER?
70%
WHEN ARE IBEW L.U. 86 MEMBERSHIP MEETINGS HELD?
SECOND WEDNESDAY OF EVERY MONTH
A ___ IS A DEVICE THAT CONTROLS ONE ELECTRICAL CIRCUIT BY OPENING AND CLOSING CONTACTSIN ANOTHER CIRCUIT OR THE SAME CIRCUIT.
RELAY
WHAT IS THE NAME OF RICKY'S GREEN CAR
SHITMOBILE
WHAT IS THE MOST COMMON TYPE OF INDUCTION MOTOR IN USE TODAY?
SQUIRREL CAGE
WHAT IS THE LINE AMPACITY FOR A SINGLE PHASE 120/240 VOLT LOAD WITH A TOTAL CALCULATED LINE LOAD OF 45,360 VOLT AMPS
189 AMPERES
WHAT IS THE ADDRESS OF THE LOCAL 86 UNION HALL?
2300 EAST RIVER ROAD
WHAT CONTACTS IN A MOTOR STARTER OPEN DURING AN OVERLOAD TO KILL POWER TO THE COIL?
OVERLOAD RELAY CONTACTS
WHAT IS BUBBLE'S MAIN SOURCE OF INCOME?
STEALING, REPAIRING, AND SELLING SHOPPING CARTS
A ______ MOTOR IS A MOTOR TYPICALLY USED FOR SMALL MECHANICAL LOADS, HAVE VERY LOW STARTING TORQUE, AND ARE GENERALLY 1/20 HP OR LESS.
SHADED POLE
WHAT IS THE MAXIMUM SIZE DUAL ELEMENT FUSE THE NEC ALLOWS TO PROTECT A 230 VOLT 3 PHASE 25 HORSE POWER MOTOR?
125 AMP
T430.250
T430.52
T240.6(A)
WHO IS THE ASSISTANT BUSINESS MANAGER FOR IBEW LOCAL 86?
RAYMOND RYERSE
WHAT WOULD BE THE MAXIMUM CURRENT AVAILABLE FOR A 120 VOLT CONTROL CIRCUIT SUPPLIED BY A 200 VA TRANSFORMER? ROUND TO TWO DECIMAL PLACES.
1.67 AMPS
200 ÷ 120= 1.67
WHAT IS RANDY'S FAVORITE FOOD?
CHEESEBURGERS
WHAT IS THE SPEED OF A 6 POLE MOTOR OPERATING AT 60 HERTZ
1200 RPM
(120 x Frequency) ÷ (# of poles)
WHAT IS THE MINIMUM SIZE COPPER GROUNDING ELECTRODE CONDUCTOR FOR A 55 KVA 3 PHASE TRANSFORMER WITH 3 x #2 COPPER AWG PRIMARY CONDUCTORS, 3 x 300 KCMIL UNGROUNDED SECONDARY CONDUCTORS, PROTECTED WITH A 250 AMP OCPD ON THE SECONDARY?
#2 AWG COPPER
WHO IS THE ORGANIZER FOR LOCAL 86?
SCOTT MILLER
TWO OUTPUTS THAT ARE PREVENTED FROM BEING ENERGIZED SIMULTANEOUSLY VIA NORMALLY OPEN CONTACTS ASSOCIATED WITH OPPOSITE OUTPUTS ARE SAID TO BE __________.
ELECTRICALLY INTERLOCKED
WHEN RICKY AND JULIAN FAIL TO GET BUBBLES THE RUSH CONCERT TICKETS THE BOYS CONCEIVE OF AN IDEA TO SNEAK INTO THE CONCERT. WHAT IS THEIR FIRST PLAN TO SNEAK INTO THE RUSH CONCERT?
THROUGH THE SEWERS
NAME THHE TWO TYPES OF WINDINGS FOUND IN A SINGLE PHASE MOTOR
START WINDING
RUN WINDING