Who or What
All Things
Learn the Dance
Energy Isolation Device (yes or no)
Where or What
100

May be a full time Pacific Power employee or hired to act as a project manager.

Authorized Employee

100

RED

The primary color of the Clearance, "Do Not Operate Tag"


100

Boundary Expansion           (2 step)

1. Operator will add the point to the log sheet and hang the tag on the device.

2. All workers issued the tagout will review the point and sign the tag.

100

Check Valve

NO

100

Fish Facility, Warehouse, Office Building

Non-Generating Facility

200

Authorized Employee, Qualified Employee and Qualified Worker

Operator

200

Danger Do Not Operate Tag

From memory detail what information is written on this tag.

Tagout log no, Date, Tag Point #, Tag__of __, Energy Isolation Description, Position of Device, Back-place for signatures

200

Energized Work                 (4 step)

If Tagout is not practical or cannot be de-energized.

1. Communicate with QE

2. Notify Duty Supervisor

3. Log event in plant logbook

4. Complete Energized Work Permit

200

4 tags for one Isolation Device

Yes.  One tag for each phase of a three phase Fused Disc and one Signature tag at accessible location.

200

Remote Tagout Location in your area(s) of operation.

Hydro North Remote Locations:

 Wallowa Falls  Bend  Big Fork

 Hydro East Remote Locations:

 Lifton  Paris Ashton Granite StairsVeyo Sandcove Gunlock

 Hydro South Remote Locations:

 Black Cap Solar

300

Successfully completed full Tagout training designated for tagout responsibilities for Non-Plant Personnel.

Pacific Power Representative

300

Record Retention

Current year plus one year for most everything.

300

Terminal Clearance            (5 step)

1. Position isolation device.

2. Hang Clearance Tag

3."Terminal Clearance" in nature of work column

4. Hang Tagout tag on top of Clearance Tag

5. Remove Tagout tag and then Clearance tag

300

Racked out CB

Double Jeopardy.

Where to hang the tag

300

Denotes the area of energy isolation.

Tagout Boundary

400

Authorized Employee who verifies that the Tagout provides protection to complete work.

Qualified Worker

400

Section 5.13 "Group Tagging Device or Master Tag"

Non-Plant Personnel sign on sheet is for the purpose of the Tagout Procedure considered a group tagging device or master tag.

OSHA reference 1910.269(d)(8)(ii)(D)

400

Boundary Reduction         (4 step)

1. Stop work and release Tagout.

2. Remove tags and Position devices as needed. 

3. Removed tags will be marked off the tagout log sheet and tags destroyed.

4. Follow section 8.8-8.11 to sign back on the modified tagout.

400

Personal Protective Grounds

No. Will not be included in the tagout as an Energy Isolation Device.  (Section 4.5) Installation and removal are recorded in proper section.

400

Used to call attention to unusual conditions and convey information. Must contain name of person hanging, date and explanation.

Yellow Tags

500

Non-Plant Personnel (list 3 types of worker)

1. Doing work requiring protection, 2. Not regularly employed at that location, 3. Has not successfully completed FULL tagout training, 4. Non-represented employees, 5. Covered by different bargaining unit.

500

Procedure in place to enable the release of an issued Tagout when the Qualified Worker is at a different location.

Off Duty-Off site Release

(contact vs no contact)

(Extra 500 points to explain the procedure!)

500

Release for Test                  (4 step)

1. QW and QE discuss nature of test, equipment line up and tags to be removed.

2. All must stop work and release the tagout.

3. Remove tags and conduct test.

4. Follow section 11.2-11.12

500

Pond elevation

Stoplogs providing energy isolation but there is a potential of overtopping with a high pond level.  How do you solve this problem?  Group will determine if answer is sufficient.

500

Found: Multiple Off Duty releases, "clean up the book", "grounds removed section-completed correctly"

Found during a Tagout Audit