4.1 Grounding Distribution Lines
3.1 Rubber Gloves
8.1 General Overhead Safety
Trucks
3.3 Basic PPE
100

When installing an eq pole bond to a wood pool that doesn't have a pole ground, how long should your number six copper be and how many inches should the staples be apart?

What is 4' long minimum and 12" on staples. 

100

What color is associated with class 2 rubber gloves?

What is Yellow? 

100

When two or more workers are working within reach of each other, they may not work on what at the same time?

What is phase or potentials?

100

What must be placed by the wheels when parked if your truck and dual rear wheels?

Wheel chocks?

100

How often should guys on the line crew change their hard hat liners?

What is a year from the date it is installed? 

200

What are the three options to bond a wood pole to grounding scheme? 

What is existing pole ground, installing a 4' piece of copper stappled 12", and a cluster bar?

200

What voltage are class 2 rubber gloves rated too?

What is 17 kV phase to ground?

200

Live line tools used for switching must be at least how long?

What is 6'

200

What book must be filled out every morning before you use your truck?

What is pretrip or logbook?

200

What class vest must be worn to flag traffic? 

What is class 3?

300

When working on a de energized and grounded line what PPE should be worn by the worker on the ground.

What is FR clothing, hard hat, safety glasses, steel toe boots, rubber gloves. 

300

Do you have to wear rubber gloves while operating ABS from the ground?

What is Yes? 

300

What stick attachment is approved for bring barrels to and from the ground with a telescopic stick?

What is talon?

300

Where should you keep your fire extinguisher card, and how often should you check off your card? 

What is inside your truck binder and monthly?

300

What type of gloves must be work while handling wood materials

What is leather gloves?

400

When working on a three-phase line and you have one phase burnt down. How many grounds are required to bring everything in ground scheme to the same potential? 

What is 4?

400

Rubber gloves are tested every ____ months by the Rubber Goods Test Lab.

What is 4?

400

Workers must use a properly rated load break tool when opening any distribution voltage, non-load break and stick operated disconnect with a load of more than how many amps?

What is 10?

400

When should you wear your seatbelt?

What is anytime the truck is in motion even in the yard?

400

How many decibels requires double hearing protection 

What is 104?

500
What is the maximum distance ground heads be placed apart from each other during the daisy chain method?

What is three inches? 

500

Which part of the gloves do the majority of failures occur while being testing at rubber goods test lab?

What is the cuff area? 

500

What is the maximum voltage you can work from a wood pole while climbing with a rubber gloved hand? 

What is 600 volts?

500

How often should of wax your boom on the bucket truck?

what is when it does not bead water?

500

if you use your hard hat one day a week or less how often do you have to replace your liner?

What is 3 years?