Commercial Garages
Aircraft Hangars
Motor Fuel Dispensing Facilities
Motor Fuel Dispensing Facilities Cont.
100

The classification of Parking Garages.

Unclassified (511.3(A))

100

Code describing the scope of Aircraft Hangar requirements.

513.1

100

Code describing the Provisions for Maintenance and Service of Dispensing Equipment.

514.13

100

Code describing the Closed Construction of floating docks, piers, and wharfs and their classification information.

514.3(D)

200

Code describing Wiring and Equipment for Portable Lighting Equipment in Class 1 Locations.

511.4(B)(2)

200

(T/F) Lampholders of metal-shell,fiber lined types shall be used for fixed incandescent lighting.

False (513.7(D))

200

Code describing the Emergency Electrical Circuit Disconnects.

514.11(A)

200

Table describing the Electrical Equipment Classified Areas for Dispensing Devices.

514.3(B)(2)

300

Underground wiring below a Class 1 Location must be installed in these.

Threaded RMC or IMC (511.8)

300

Code describing Special Portable Lighting equipment requirements.

513.10(E)(1)

300
Classification (Class and Division) within 5ft of open end of an underground tank vent, extending in all directions

Class 1 Division 1(T514.3(B)(1))

300

Code describing the requirements for Wiring and Equipment above Class 1 Locations.

514.7

400

Classification (Class and Division) of Lighter-than-Air fuel major repair garages within 18in of the ceiling.

Class 2 Division 2 (511.3(D))

400

Classification (Class only) when above the floor, of Uninterrupted raceways that are embedded in a hangar floor.

Class 1(513.8(B))

400

(T/F) Grade level means the surface of a pier,extending down to water level for marine applications.

True (T513.3(B)(1)(Ex))

400

Classification (Class and Division) of the entire space within a protective enclosure for Vapor Processing Systems.

Class 2 Division 2 (T514.3(B)(1))

500

Classification of areas designed with positive air pressure, adjacent to the classified locations where flammable vapors are not likely to be released. (Lighter and Heavier-than-air locations)

Unclassified (T511.3)

500

Label text that must be permanently affixed to Mobile Stanchions with electrical equipment complying with 513.7(E).

WARNING
KEEP 5FT CLEAR OF AIRCRAFT ENGINES
AND FUEL TANK AREAS

(513.7(F))

500

Classification (Class and Division) of the entire space within any pit indoors located at remote pumps.

Class 1 Division 1 (514.3(B))

500

(T/F) PVC, RTRC, and HDPE conduits shall not be permitted where buried under more than 2ft of cover.

False (514.8(Ex2))