Wiring
NEC
Ampacity
Blueprints
MISC
100

most common type of conduit used

What is EMT

100

NEC 422.13 requires that the branch circuit for a storage type electric water heater with a capacity of 120 gallons or less to be a ________ load.

What is Continuous

100

The allowable ampacity of a 4 AWG THHN conductor is 95 amperes. If we have four 4 AWG conductors, what is the adjusted ampacity?

What is 76

100

In commercial-type building the common 3-phase system with the highest voltage with the highest voltage is the ________. 

What is 480 Y

100

The construction plans for a building are often called _________

What are blueprints
200

Kinds of boxes used in Commercial electirical

What is Metallic Boxes

200

In the areas where ________ is enforced, the NEC is the law.

What is OSHA

200

What is the adjustment factor for 22 current carrying conductors?

What is 45A
200

The ____________ lists all of the electrical symbols that are used in this set of drawings 

What is Electrical Symbol Legend

200

A switch symbol without a number beneath the horizontal line means that a ______ switch should be installed

What is single-pole

300

Trade size 3 metric designator

What is 78

300

NEC 430.24 requires that the conductors supplying several motors on one circuit shall have an ampacity of not less than ________ percent of the largest motor plus the full-load current rating of all other motors on that circuit?

What is 125

300

For a five conductor setup in a single raceway, the ampacity of a siza 10 AWG type THHN conductor will be ________ amperes 

What is 32

300

In the commercial blueprints, what is the astronomical clock used for 

What is Entrance Luminaires

300

Qualified Person 

What is one who has demonstrated skills and knowledge related to the construction and operation of electrical equipment and installations and has received safety training to identify and avoid the hazards involved.

400

The maximum amount of conductors allowed in a raceway without having to account for ampacity adjustment

What is 3 conductors

400

When using cable for the wiring of three way switches, NEC 200.7 C (2) permits the use of a conductor with insulation that is white or _____ or has three continuous white stripes as a switch supply only if the conductor is permanently re-identified?

What is grey

400

What are the 3 different temperature ratings used for ampacity corrections?

What is 60 C (140 F), 75 C (167 F), 90 C (194 F)

400

The boiler heating circuit has 2 main lugs connected to two _________ per phase conductor

what is 500 kcmil 

400

What steps should be taken while tabulating materials to ensure the best possible outcome

What is determine the lengths of conductors needed, figure out panel board locations, make special notes for longer runs, be organized and meticulous

500

How are insulated grounding receptacles wired

Insulated grounding conductors have a separate grounding conductor ran straight to ground without being tied with any other grounding conductor

500

A sign outlet is assigned a minimum allowance of ______ volt-amperes for each branch circuit required?

What is 1200

500

What is the ampacity for five 3 AWG THWN wires that have a continuous load

What is 64 A

500
What kind of elevator is used in the blueprints. 

What is machine-room-less, (page 254 commercial book)

500

Thermoset insulation description

What is conductor that is moisture resistant, flame retardant, nonmetallic covering usable in Dry and damp locations. Type letter RHH and a maximum of 90 C or 194 F