On what drawing would you find the cooling capacity for a condenser unit?
M4.1
Identify the room that the water meter is located.
Mechanical
1:111
MP2.2, KN 6, A2.1
Who is responsible for the mounting height of the light fixtures in room 1:101
Architect
Identify the manufacturer and wattage for the baseboard heater H10.
Ouellet Stelpro 1000W
E6.1 - Elect Heater Schedule
Identify the circuit and switch for the electrical outlet in Stair A 1:113.
PA-3 Col 3 LHS
EP2.1, A2.1
Identify the size of the supply duct for room 1:109.
400X200mm
MH2.2, KN#6, A2.1
Identify the side of the building that has the incoming sprinkler system coming in.
East (near GL 1 between GL B and C)
MF2.1, KN 4
MP2.1 KN 9
Identify the quantity of LED01light fixtures required on the exterior of the building.
24
E1.2, E6.2
Identify the rooms that require CCTV camera.
1:100 - Entry
1:110 - Maintenance
1:113 - Stair A
1:105 Stair B
A2.1, EP2.1
In what room would you find distribution panel T500.
CRU01B
1:107
E6.5
Identify the quantity of condensing units installed in the crawl space
2 installed
CU2-10
CU3-10
neither service the crawlspace.
M4.1, MH2.1
How many pendant sprinklers are to be installed on the second floor?
15
MF2.1 - legend
MF2.2 - dark circles
What is the control device type used to turn the lights on and off in the UTR washroom?
OS - occupancy sensor
E6.1 - schedule
List all of the devices required for room 1:100.
2 fire alarm horn/strobe
ADO with push
Electric strike
CCTV camera
Annunciator panel
Enterphone
2 Card readers
4 Door contact alarms
Recessed heater
EP2.1, E1.1
Identify the circuit the exhaust fan motor is located on the roof.
PA44 and 45
EP2.4, E6.2
Identify the quantity of thermostats required for the second floor.
10
1 per coil
MH2.3
Identify the plumbing services located in the vertical shaft between the first and second floor near Stair B.
DCW - domestic cold water
DHW - domestic hot water
RWL - rain water leader
IW - indirect waste
Sanitary
MP2.1
MP2.2
Identify the quantity of EMR2 fixtures required for the crawlspace.
11 - Emergency battery light - decorative remove head
Hint: "R" is a type
EL2.0, E6.2
Identify the type and quantity of fire protection systems required for Hallway 2A and 2B.
2 fire alarm horn/strobe
1 sprinkler valve
1 sprinkler flow switch
3 duct smoke detectors
2 FA pull stations
E1.1 schedule, EP2.2
What is the amperage of the breaker for circuit TK-12.
20 amp
E6.7