Magnetism & Induction
3 Phase Motors
Miscellaneous
Sizing Motor
Sizing Motor
100

Electromagnetism is used to convert electrical energy into?

Rotating mechanical force.

100

____ is the stationary part of an AC motor that converts electrical energy to the energy of a magnetic field?

Stator

100

A ____ is a device that stores an electrical charge?

Capacitor

100

What article in the NEC refers to Motors, Motor Circuits, and Controllers?

Article 430

100

When unsure to use the Table FLC or Nameplate FLA refer to what NEC section?

430.6(A)(1) & (2)

200

Mutual Induction

200

How do you change the direction of rotation of 3 phase motor?

Interchanging any two of the 3-phase power lines to the motor.

200

A ____ is an electric switch that operates using the centrifugal force created from a rotating shaft which opens the switch and breaks the electrical connection?

Centrifugal Switch

200

Calculate the minimum ampacity for the motor branch circuit conductors at 460v.

Table 430.250 = 

7.6 amps x 125% = 9.5 amps

200

What sections of NEC refers to motor disconnecting means? 

430.101 through 430.113

300

What happens when an AC sine wave crosses the zero point?

Positive to negative, Magnetism reverses

300
Actual voltage applied to a motor should be within ___% of the motors nameplate rated voltage?

10%

300

What is this drawing representing?

Low Voltage Wiring

300

What size inverse-time-circuit breaker is used for branch-circuit short-circuit and ground fault protection? 230v

Table 430.250 = 15.2 amps

Table 430.52 = 250%

 = 38 amps = 40amp breaker

300

What is the maximum rating of the motor branch-circuit short-circuit and ground-fault protection using time delay fuses?

Table 430.248 = 28 amps

Table 430.52 = 175%

= 49 amps = 50 amp fuse

400

What are the requirement of induction?

A conductor, magnetic field, and relative motion. 

400

What are the two major components of a magnetic motor starter?

Contactor and Overload Relay

400

This equation represents _____?

Output Power / Input Power = 

Motor Efficiency

400

What is the minimum current rating of the motor disconnecting means?

Table 430.248 = 28 amps

430.110(A) = 115%

28 x 115% = 32.2 amps

400

Determine the maximum overload protection using overload relays? 208v

430.32(A)(1) Separate Overload Device

40°C rise, 1.15 SF = 125%

Nameplate FLA = 21 amps

21 x 125% = 26.25A

500

What does the Left Hand Conductor Rule describe?

The direction of a magnetic field around a conductor relative to the direction of the current in the conductor.

500

Apparent power is measured in ____?

Volt amperes or Kilovolt amperes

500

Name to parts of a magnetic motor starter.

Top Half of starter = ___?

Parts of top half = ___ ___ ___?

Bottom Half of starter = ___?

Parts of Bottom Half = ___ ___?

Contactor

Coil, Rated Contacts, Holding Contacts.

Overload Relay

Heaters, NCOL

500

A 230-volt, 3-phase, 25-horsepower squirrel-cage motor and a 230-volt, 30-horsepower synchronous motor are installed on the same motor branch circuit. What is the minimum ampacity of the conductors for this single branch circuit?

Table 430.250, 3-phase
25 hp squirrel-cage = 68 A FLC
30 hp synchronous = 63 A FLC
430.24, branch circuit ampacity = (largest FLC × 125%) + other(s)
     = (68 × 1.25) + 63
     = 85 + 63
     = 148 A

500

What is the maximum standard rating for a time-delay (dual-element) fuse permitted to be used for motor branch-circuit short-circuit and ground-fault protection for a 10-horsepower, 208-volt, single-phase capacitor motor when starting current is a problem?

Table 430.248, single-phase motor
10-hp, 208 V = 55 A
Table 430.52(C)(1), Exception No. 2(b)
Time-delay dual-element fuse = 225%
Rating = 55 × 2.25 = 123.75 A
Next lower standard size OCPD
240.6(A) standard size = 110 A