A receptacle shall not be more than 20ft from the inside wall of the pool and not closer then _ft.
What is 6?
This is a system or circuit conductor that is intentionally grounded.
What is a Grounded Conductor?
Service Masts supporting Overhead Service Conductors shall be of adequate strength or be supported by __.
What is Braces or Guy Wires?
This article is for Swimming Pools, Fountains, and Similar Installations.
What is Article 680?
We use this table to find allowable ampacitity for NM(Romex) and THHN.
What is Table 310.16?
This shall not be closer than 5ft, but within sight, of the inside edge of the pool or hot tub.
What is disconnecting Means?
This table shows the minimum size Equipment Grounding Conductors.
What is 250.122?
Overhead Service Conductors over residential properties and driveways shall have a clearance of at least __ft.
What is 12?
This article is for Conductors for General Wiring.
What is Article 310?
NM Cable (Romex) can only be sized in this degree column.
What is 60 degrees C?
This is the minimum solid copper conductor size to bond pool shells, reinforcing steel, and perimeter surfaces.
What is 8AWG?
This table shows the minimum size grounding electrode conductor to be connected to the grounding electrode system.
What is 250.66?
This is the minimum distance for service conductors from a window.
What is 3?
This article is for Luminaires, Lampholders, and Lamps.
What is Article 410?
Conduit 24” or less can be filled up to this percentage.
What is 60%?
This is required to reduce voltage gradients in the pool area.
What is Equipotential Bond?
If installed in RMC, IMC, Schedule 80 PVC, or EMT, then we can install this minimum size copper Grounding Electrode Conductor.
What is 8 AWG?
Service Disconnecting Means shall not be installed in this location.
What is a bathroom?
This article is for Hazardous Locations, Classes I, II, and III, Divisions 1 and 2.
What is Article 500?
For Box Volume, a 1/4 volume allowance shall be made for each additional equipment grounding conductor that exceeds _.
What is 4?
Overhead power conductors over a pool or hot tub shall have a minimum clearance of __ft over the top water level.
What is 22.5?
This table is for minimum size Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and Supply-Side Bonding Jumper.
What is 250.102?
Overhead Service Conductors can be installed 3 feet above a roof if the roof has this pitch or greater.
What is a 4 in. in 12 in. (4-12 pitch)?
This article is for General Requirements for Wiring Methods and Materials.
What is Article 300?
Single Family Dwelling Services rated 100-400 Amps shall have Service Conductors with an amperage not less than __% of the service rating.
What is 83?