Wet Systems
Dry Systems
Preaction and Deluge
Antifreeze
Surprise Me
100

Pressure gauges shall be installed _______ on alarm checks or system riser checks

What is above and below

100

This is required in valve rooms of dry systems.

What is light and heat?

100

The heat source shall be of this type.

What is permanently installed?

100

Unless permitted, anitfreeze shall be this; a list published by an organization that is acceptable to the AHJ.

What is listed?

100

Pipes and fittings installed on the exterior of the building or structure shall be this.

What is corrosion resistant?
200

Relief valves hall be provided, unless 7.1.2.2 is met, and set to this.

What is 175psi

200

This type of system is not allowed on a dry system.

What is gridded?

200

Not more than this many sprinklers shall be controlled by any one pre-action.

1000

200

a drain/test connection shall be installed at this location.

What is most remote portion of the system?

200

In regards to outdoor sprinklers, manually controlled open sprinklers shall be used only when this.

What is where constant supervision is present?

300

Wet systems shall be permitted to supply dry, preaction or deluge systems provided this.

What is adequate water supply?

300

One foot of 6in pipe holds about this much water.

What is 1 and a half gallons?

300

Sprinkler piping and fire detection devices shall be automatically supervised where more than this many sprinklers are installed.

What is 20?

300

This is installed to prevent thermal expansion.

What is a listed expansion chamber?

300

 Branch lines installed in refrigerated spaces shall be pitch to this?

What is 1/2" for every 10ft?

400

A single air vent with a connection conforming to 8.16.6 shall be provided on each of these.

Wet pipe systems utilizing metallic pipe.

400

A system of this size of not more than this shall be permitted a quick opening device and not be required to meet water delivery time.

What is 750gal?
400

Preactions shall be of these three types.

What is Single interlock, double interlock, and non-interlock.

400

This type of antifreeze shall be permitted with ESFR sprinklers.

What is premixed solutions of propylene glycol?

400

A strainer shall be provided in the riser of feed mains that supplies sprinklers having K-factors smaller than this.

What is K-2.8.

500

This can be used in lieu of heated valve enclosures to protect valve and supply pipe from freezing

What is nothing.

500

Extra Hazard calculations for dry pipe systems shall be 2 remote sprinklers and this delivery time.

What is 45?

500

Preactions as defined in 7.3.2.1 (2,3) shall have a minimum supervisory pressure of this psi

What is 7?

500

Placards shall be placed on the antifreeze system main valve that indicates this.

What is manufacture type and brand, concentration by volume and the volume of solution?

500

In regards to dry pipe systems, approved gas can be from storage containers sized to provide a supply for this amount of time of expected maintenance.

What is 6 months?