FIRE PUMPS
WET SYSTEMS
DRY SYSTEMS
PREACTION SYSTEMS
SPRINKLER HEADS
100

The valve that cools a fire pump when it is deadheading.

What is Casing Relief Valve?

100

The device that triggers a alarm on a wet sprinkler system? 

What is Waterflow Switch

100

The area in which a dry system would be installed.

What is Unheated -cold areas?

100

The minimum temperature a pre-action valve enclosure must be kept.

What is 40deg F?

100

The type of sprinkler heads used in homes.

What is Residential Sprinkler?

200

The gauge that shows the incoming pressure on a fire pump.

What is Compound Suction Gauge?

200

This amount of revolutions a hand wheel on a control valve should be moved that triggers a supervisory alarm?

What is 2-3 Revolutions

200

Systems with a capacity of _____ or less are not required to meet specific water delivery time requirements

What is 500 gallons?

200

The frequency priming water level should be tested on a pre-action valve.

What is Quarterly?

200

 A recessed sprinkler with a cover plate

What is Concealed?

300

This is going to protect you from the rotating assembly on a fire pump.

What is Pump Shaft Coupling Guard?

300

The frequency all control valves should be visually inspected

What is Weekly?

300

Allowable time for air compressor to replenish system air pressure.

What is 30 minutes?

300

The frequency pre-action valve gauges should be inspected.

What is Weekly?

300

CMSA stands for this.

What is Control Mode Specific Application? 

400

The frequency a full flow pressure test should be performed on a fire pump.

What is Annually?

400

This is the only valves that do not need to be locked, sealed or electrically supervised.

What is Hose Valves?

400

Allowable time for water delivery at the most remote point of a dry system light hazard.

What is 60 seconds?

400

The frequency a pre-action system should be tested for air leakage.

What is 3 years?

400

The purpose of an institutional head.

What is provide fire safety while preventing vandalism, tampering, and self-harm (including suicide) by using tamper-resistant, anti-ligature design?

500

The part on a fire pump that will prevent possible cavitation of the pump.

What is Automatic Air Release ?

500

This is the frequency pressure gauges should be inspected or calibrated.

What 5 Years?

500

A device used to speed up trip time of a dry valve if water delivery is greater than 60 seconds by venting air directly out of the system.

What is an exhauster?

500

The amount of time a full flow test of a pre-action system should not exceed.

What is 3 years ?

500

This guy is credited with the invention of the sprinkler head.

Who is Henry Parmalee?