The valve that cools a fire pump when it is deadheading.
What is Casing Relief Valve?
The device that triggers a alarm on a wet sprinkler system?
What is Waterflow Switch
The area in which a dry system would be installed.
What is Unheated -cold areas?
The minimum temperature a pre-action valve enclosure must be kept.
What is 40deg F?
The type of sprinkler heads used in homes.
What is Residential Sprinkler?
The gauge that shows the incoming pressure on a fire pump.
What is Compound Suction Gauge?
This amount of revolutions a hand wheel on a control valve should be moved that triggers a supervisory alarm?
What is 2-3 Revolutions
Systems with a capacity of _____ or less are not required to meet specific water delivery time requirements
What is 500 gallons?
The frequency priming water level should be tested on a pre-action valve.
What is Quarterly?
A recessed sprinkler with a cover plate
What is Concealed?
This is going to protect you from the rotating assembly on a fire pump.
What is Pump Shaft Coupling Guard?
The frequency all control valves should be visually inspected
What is Weekly?
Allowable time for air compressor to replenish system air pressure.
What is 30 minutes?
The frequency pre-action valve gauges should be inspected.
What is Weekly?
CMSA stands for this.
What is Control Mode Specific Application?
The frequency a full flow pressure test should be performed on a fire pump.
What is Annually?
This is the only valves that do not need to be locked, sealed or electrically supervised.
What is Hose Valves?
Allowable time for water delivery at the most remote point of a dry system light hazard.
What is 60 seconds?
The frequency a pre-action system should be tested for air leakage.
What is 3 years?
The purpose of an institutional head.
What is provide fire safety while preventing vandalism, tampering, and self-harm (including suicide) by using tamper-resistant, anti-ligature design?
The part on a fire pump that will prevent possible cavitation of the pump.
What is Automatic Air Release ?
This is the frequency pressure gauges should be inspected or calibrated.
What 5 Years?
A device used to speed up trip time of a dry valve if water delivery is greater than 60 seconds by venting air directly out of the system.
What is an exhauster?
The amount of time a full flow test of a pre-action system should not exceed.
What is 3 years ?