Know The Lingo
Fundamentals
When Does It Happen
Paper Trail
Unknown
100

What is the definition of Acknowledge?



3.3.5 Acknowledge 

An action performed by a person to confirm that a message or signal has been received. 



100

 The annunciation of an alarm signal at the protected premises shall occur within ____ seconds after the activation of an initiating device.

A. 90 Seconds 

B. 5 Seconds 

C. 10 Seconds 

D. 30 Seconds 

10.11.1

C. 10 seconds

100

When are Emergency control functions tested?

A. Annual

B. Semi-annual 

C. Quarterly 

D. Bi-weekly 

Table 14.4.3.2 Testing (24)

A. Annual

100

What Code Reference refers to Design (Layout) documentation?

A.7.7

B.3.5

C.7.5

D.7.3

D.7.3

100

Visible and audible indication of latching supervisory signals shall be indicated within ___ seconds at the locations specified.

A. 90 Seconds 

B. 200 Seconds

C. 100 Seconds

D. 60 Seconds

10.14.1


A. 90 Seconds 

200

What is the definition of a Protected Premises (Local) Control Unit?



3.3.115.2

A fire alarm control unit that serves the protected premises or a portion of the protected premises.

200

The secondary power supply for in-building fire emergency voice/alarm communications service shall be capable of operating the system under quiescent load for a minimum of ____?

A. 5 Minutes 

B. 15 Minutes 

C. 12 Hours 

D. 24 hours

10.6.7.2.3 

D. 24 hours

200

At what frequency are Lamps and LEDs inspected on a fire alarm systems unmonitored for alarm, supervisory, and trouble signals?

A. Semi-Annual 

B. Annual

C. Weekly

D. Quarterly 

Table 14.3.1 Visual Inspection (2.C)

C. Weekly

200

Where would you find information for Shop drawings?

Code Reference _____.

7.4 

200

What does NFPA 170 cover?

Standard for Fire Safety and Emergency Symbols

300

What is the definition of a Level Ceiling? 

3.3.40.1 Level Ceilings.

What is Ceilings that have a slope of less than or equal to 1 in 8.

300

A record of the impairments shall be maintained by the system owner or the owner’s designated representative for a period of ____ from the date the impairment is corrected.

10.21.2

What is 1 Year

300

What type of Detector is this? After 15 years from initial installation, replace all devices or have 2 detectors per 100 laboratory tested. Replace the 2 detectors with new devices. 

A. Fixed-temperature, nonrestorable spot type

B. Fixed-temperature, nonrestorable line type 

C. Restorable line type, pneumatic tube only 

D. Duct Detector 

Table 14.4.3.2 Testing (17.4.C)

A. Fixed-temperature, nonrestorable spot type

300

All record documentation shall be stored in the documentation cabinet. No record documentation shall be stored in the control unit. 

A. True

B. False

Code Reference? ________

7.7.2.3

A. True



300

Level 1 pathways shall use equipment that is dedicated to the life safety system.

A. True

B. False 

12.5.4

B. False (Level 3)


400

What is the definition of a Unit (Multi-Cell)?


3.3.43.3 

Multiple cells in a single container, such as a 12-volt unit composed of six 2-volt cells.

400

The secondary power supply shall automatically provide power to the supervising station facility and equipment within ___ seconds whenever the primary power supply voltage is insufficient for required system operation.

A. 15 Seconds

B. 10 Seconds

C. 45 Seconds

D. 60 Seconds 

10.6.6.2

D. 60 Seconds

400

At what frequency is circuit integrity on a Nonmetallic pathway tested at?

A. Annual

B. Semi Annual 

C. Quarterly 

D. Monthly 

Table 14.4.3.2 Testing (16.2)

A. Annual

400

Required documents regarding system design and function shall be maintained for how long?

A. 1 Year

B. 4 years

C. 10 years

D. The life of the system 

7.7.1.4

D. The life of the system 

400

What Classes of wiring have redundant paths? (Select all that apply)

A. Class B

B. Class A 

C. Class D

D. Class X 

A. Class A 12.3.1

D. Class X 12.3.7

500

What is the definition of a Spark/Ember Detector?


3.3.77.22

A radiant energy–sensing fire detector that is designed to detect sparks or embers

500

Personnel programming a system shall be certified by the _________________________.

A. Authority Having Jurisdiction

B. System Manufacturer 

C. State or Local Jurisdiction

D. NICET

10.5.3.5.1

B. System Manufacturer

500

For systems with restorable fixed-temperature, spot-type heat detectors tested over multiple years, records shall be retained for the __ year of testing and for __ year thereafter. 

A. 10,2

B. 5, 1

C. 10,1

D. 5,2

14.6.2.2 

B. 5, 1

500

A copy of the site-specific software shall be stored on-site in _____________.


 

7.5.7.2 

Nonvolatile memory.

500

Which type of pathway shall be designated if it has a fail safe operation?

A. Class A

B. Class B

C. Class D 

D. Class E

12.3.4

C. Class D