A document that is advisory or informative.
what is a GUIDE
MEDICAL AIR SHALL NOT POWER THIS.
What is a VENTURI.
AREA ALARMS SHALL BE LOCATED HERE.
What is a NURSES STATION OR OTHER SIMILAR LOCATIONS THAT PROVIDE SURVEILLANCE.
HOSE AND FLEXIBLE CONNECTORS SHALL BE SUITABLE FOR THIS PSIG.
What is 300 PSIG.
THIS WILL BE THE FIRST THING YOU DO WHEN YOUR INSTALLATION OF DISTRIBUTION PIPING IS DONE.
what the INITIAL BLOW DOWN.
AN EXTENSIVE COMPILATION OF PROVISIONS THAT IS SUITABLE FOR ADOPTION INTO LAW.
What is a CODE
PERMANENT PARTICULATES CAN BE SIZED TO THIS.
What is 1 MICRON.
AREA ALARM PANELS MONITOR PRESSURE INCREASE OR DECREASE BY THIS PERCENTAGE.
What is 20%
A PRESSURE OF 160 psi - 185 psi IS COMMON FOR THIS GAS.
What is NITROGEN, INSTRUMENT AIR or SUPPORT GAS.
THIS WILL BE DONE BEFORE INSTALLATION OF STATION OUTLETS/INLETS ROUGH IN ASSEMBLIES AND OTHER SYSTEM COMPONENTS (PRESSURE/VACUUM ALARM DEVISES , INDICATORS, PRESSURE RELIEF VALVES, MANIFOLDS, AND SOURCE EQUIPMENT.
What is the INITIAL BLOW DOWN.
INDICATES A MANDATORY REQUIREMENT.
What is SHALL
MEDICAL AIR SHALL MEET THE REQUIREMENTS OF THESE THREE LETTERS.
What is USP.
AN INCREASE OR DECREASE IN PRESSURE WILL BE SENT TO THESE TWO ALARM PANELS.
What is AREA and MASTER.
INSTRUMENT AIR SOURCES SHALL BE CAPABLE OF PRODUCING NO LESS THAN THIS PSI.
What is 200 PSI
AFTER THE INITIAL BLOW DOWN AND PRIOR TO INSTALLATION OF OF COMPONENTS OF THE DISTRIBUTION THAT WOULD BE DAMAGED BY A TEST PRESSURE OF 150 PSI.
What is the INITIAL PRESSURE TEST.
A DOCUMENT, THE MAIN TEXT OF WHICH CONTAINS ONLY MANDATORY PROVISIONS USING THE WORD "SHALL" TO INDICATE REQUIREMENTS.
What is a STANDARD.
MEDICAL AIR COULD ALSO BE MADE FROM THESE TWO GASSES.
What is OXYGEN USP AND OIL FREE DRY NITROGEN USP.
ALARM INDICATION WHEN OR JUST BEFORE CHANGE OVER OCCURS IN A MEDICAL GAS SYSTEM WILL BE SENT TO THIS ALARM PANEL.
What is MASTER.
MEMORY METAL FITTINGS SHALL BE RATED FOR THIS PSI.
What is 300 PSI.
DURING THE THE INITIAL PIPING PURGE TEST YOU SHALL USE THESE.
What is the APPROPRIATE ADAPTERS.
NON-MANDATORY PROVISIONS WOULD BE FOUND HERE.
What is the APPENDIX, ANNEX, FOOTNOTE OR INFORMATIONAL NOTE.
MEDICAL AIR SHALL BE ALLOWED HOW MANY DETECTABLE LIQUID HYDROCARBONS.
What is ZERO or NO.
THIS VARIANCE OF A PERCENTAGE OF OXYGEN CONCENTRATION, IN A PROPORTIONING SYSTEM, WILL TRIGGER A LOW/HIGH AT THE LOCAL ALARM.
what 19.5 % to 23.5%
WAGD SYSTEMS OPERATE AT THIS LEVEL OF VACUUM.
What is 5 in. HgV.
THE INITIAL PIPING PURGE TEST SHALL START HERE AND END HERE.
What is the CLOSEST OUTLET/INLET TO THE ZONE VALVE AND CONTINUE TO THE FURTHEST OUTLET/INLET WITHIN THE ZONE.