CYLINDERS IN USE AND IN STORAGE SHALL BE KEPT FROM REACHING THIS TEMPERATURE.
HIGH/LOW
What is 125*F or 20*F
RESERVE HEADERS FOR MEDICAL AIR, SHALL HAVE ENOUGH ATTACHED CYLINDERS FOR THIS TIME OF OPERATION.
What is ONE HOUR NORMAL OPERATION.
INSTALLERS ARE QUALIFIED WITH THIS CREDENTIAL.
What is an ASSE 6010.
VALVES SHALL BE LOCKED OR LATCHED IN WHAT POSITION.
What is THEIR OPERATING POSITION.
AN EOSC NEEDS THIS AMOUNT OF ROOM TO CONNECT THE AUXILIARY SOURCE GAS.
What is 3 FT.
CENTRAL SUPPLY SYSTEMS FOR OXYGEN WITH A TOTAL CAPACITY CONNECTED AND IN STORAGE GREATER THAN 20,000 FT^3, SHALL COMPLY WITH THIS .
What is the NFPA 55
IN ANY CASE IN A CATEGORY 1 SYSTEM, SHALL THERE BE FEWER THAN THIS MANY COMPRESSORS.
What is 2 COMPRESSORS.
VERIFIERS ARE QUALIFIED UNDER THIS CREDENTIAL.
What is an ASSE 6030.
THIS VALVE IS INSIDE THE BUILDING IF THE SOURCE VALVE IS AWAY FROM THE BUILDING.
What is a MAIN LINE VALVE.
IN THIS CATEGORY FAILURE OF EQUIPMENT OR A SYSTEM WOULD CAUSE MAJOR INJURY OR EVEN DEATH.
What is CATEGORY 1.
CYLINDERS WHETHER FULL OR EMPTY SHALL NOT BE STORED IN ENCLOSURES CONTAINING THIS.
What is MOTOR-DRIVEN MACHINERY.
WHEN MEDICAL AIR PIPING SEPARATES AFTER THE FILTERS, BUT TWO LINES HAVE THEIR OWN LINE REGULATORS, DEW POINT MONITORS, RELIEF VALVES AND SOURCE SHUT OFF VALVES, THEY WOULD BE OPERATING AT THIS...
What are DIFFERENT OPERATING PRESSURES.
MEDICAL GAS MAINTENANCE WORKERS ARE QUALIFIED WITH THIS CREDENTIAL.
What is an ASSE 6040
IN-LINE CHECK VALVES SHALL BE MADE OF THIS MATERIAL.
What is BRASS OR BRONZE.
IN THIS CATEGORY FAILURE OF EQUIPMENT OR A SYSTEM WOULD CAUSE MINOR INJURY TO PATIENT STAFF OR VISITORS.
What is CATEGORY 2
CENTRAL SUPPLY SYSTEMS FOR BULK INERT GASSES, OF A TOTAL CAPACITY IN USE AND IN STORAGE OF 20,000 FT^3 OR MORE SHALL COMPLY WITH THIS STANDARD FOR BULK INERT GAS SYSTEMS.
What is CGA P-18
THE MEDICAL AIR RECEIVER SHALL BE PIPED IN AWAY TO ENSURE IT CAN BE SERVICED WITHOUT SHUTTING DOWN THE SUPPLY OF MEDICAL AIR
What is BYPASSED.
A PERSON WHO,BY POSSESSION OF A RECOGNIZED DEGREE, CERTIFICATE, PROFESSIONAL STANDING, OR SKILL, AND WHO, BY KNOWLEDGE, TRAINING, AND EXPERIENCE, HAS DEMONSTRATED THE ABILITY TO PERFORM THE WORK.
What is a QUALIFIED PERSON.
IN-LINE CHECK VALVES SHALL HAVE THREADED PURGE POINTS OF THIS SIZE NPT.
What is 1/8 in. NPT
FAILURE OF EQUIPMENT OR SYSTEM LOSS WOULD NOT LIKELY CAUSE INJURY, BUT MAY CAUSE DISCOMFORT TO PATIENT, VISITORS OR VISITORS.
What is CATEGORY 3.
THE PRODUCT IDENTIFICATION WRAPAROUND LABEL, FOR LIQUID CONTAINERS, SHALL HAVE LETTERING ___________INCHES HIGH.
What is 2.
FOR LIQUID RING COMPRESSORS, SERVICE WATER AND SEAL WATER SHALL BE USED OF A QUALITY RECOMMENDED BY WHO.
Who is THE COMPRESSOR MANUFACTURER.
THESE PEOPLE WILL ALLOW YOU TO STAY IN OPERATION EVEN IF YOUR NOT IN STRICT COMPLIANCE WITH THIS CODE, AS LONG AS IT DOES NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.
What is the AUTHORITY HAVING JURISDICTION.
ALL GAS DELIVERY COLUMNS, HOSE REELS, CEILING TRACKS, CONTROL PANELS, PENDANTS, BOOMS, OR OTHER SPECIAL INSTALLATION SHALL BE LOCATED DOWNSTREAM OF THIS.
What is a ZONE VALVE.
FAILURE OF EQUIPMENT OR A SYSTEM LOSS WOULD LIKELY HAVE NO PHYSICAL IMPACT ON PATIENT CARE IN THIS CATEGORY.
What is CATEGORY 4.