OFC Defined Terms
General Requirements
4.2 Container Storage & Handling & Laboratories
4.3 Storage Tanks & Tank Vehicles
4.4 Piping and Transfer
100

What is the definition of Flash point?

Flash point means the minimum temperature at which a liquid within a container gives off vapour in sufficient concentration to form an ignitable mixture with air near the surface of the liquid.

100

What date is meant by when we refer to something as existing in Part 4 of the Ontario Fire Code?

November 21,1997

100

Under the application of 4.2.1 

Containers conforming to Clause 4.2.3.1(1)(a) shall have a capacity not more than ______ 

230L

100

Atmospheric Storage tanks shall be provided with these two types of venting

Normal and emergency

100

Piping for F/C liquids shall not be painted this colour?

Red

200

What is Vapour Pressure?

Vapour pressure means the pressure exerted by a liquid as determined by ASTM D 323

200

A Class IC Flammable liquid has Flash points between this range?

22.8 degrees C and 37.8 degrees C

200

In a dwelling unit how much flammable & combustible liquids are they allowed to store?

10L

200

Storage tanks supports that exceed this measurement require a 2 hour fire separation 

300mm

200

Joints in F/C liquid piping may be of these 3 types

Welded, threaded, flanged

300

What is a Combustible liquid?

Combustible liquid means any liquid having a flash point at or above 37.8°C and below 93.3°C.

300

A fire safety plan is required when there is this amount is exceeded of Class I liquids 

250L 

300

In an industrial occupancy clearance of ____ shall be maintained between storage of F/C liquids and walls where the width of storage is greater than 1.5m

400mm

300

The minimum separation between a F/C Liquid storage tank and a liquefied petroleum gas cylinder shall be?

6m

300

Leakage testing in piping systems shall be pressure tested at pressures of not less than what.

350 kPa or 1.5 times the max operating pressure

400

What is a Tank Vehicle?

Tank vehicles means any vehicle, other than railroad tank cars and boats, with a cargo tank having a capacity of more than 450 L mounted or built as an integral part of the vehicle, used for the transportation of flammable or combustible liquids, and includes tank trucks, trailers and semi-trailers.

400

A spill control plan is required when?

4.1.6.4. (1) A spill control procedure shall be approved and implemented for any occupancy where flammable liquids or combustible liquids are stored, handled, processed or used.

400

If Class IA or IB liquids are dispensed or stored in open containers within a storage room the room shall be designed with this critical preventive structural member

Explosion venting/ Explosion Wall

400

An above ground storage tank is out of service for 150 days the valves for that tank shall be?

closed and securely locked

400

Heating of Piping systems shall NOT be done by this heat source

Open Flame

500

What is an Unstable liquid?

Unstable liquid means a liquid, including a flammable and combustible liquid, which is chemically reactive to the extent that it will vigorously react or decompose at or near normal temperature and pressure conditions or which is chemically unstable when subject to impact.

500

Mechanical ventilation is required when?

4.1.7.2 (1)(a) continuous mechanical ventilation where Class I liquids are processed, dispensed or used in a manner that releases flammable vapours into the room or enclosed space

500

In a laboratory, a separation of this fire resistance rating is required between its room and the remaining of the building 

1 Hour 4.12.2.1(1)

500

A protected 250,000L above ground storage tank containing an unstable liquid shall be separated from a building by a distance of

7.5m

500

A visual inspection routine for the prompt detection of obviously abnormal conditions shall be established and shall be performed at least this often.

Once per shift