GRD
Noise Control
Sustainable
Terminal Units
Critical Environments
100

This is the throw velocity we want at our occupied zone.

What is 40-50 fpm?

100

This product reduces noise in a duct system using baffles typically filled with insulation.

What is a silencer?

100

This is the water temp to avoid condensation on a beam coil.

What is 2-3F above dew point (or 57-58F)?

100

This is a common device used to reheat air leaving a terminal unit.

What is a Hot Water or Electric Reheat coil?

100

FFU stands for this.

What is Fan Filter Unit?

200

This model is designed for floor applications.

What is LBPH or LBMH?

200

Changing these silencer features will impact pressure drop.

What is free open area and baffle geometry?

200

This is the recommended face velocity on a displacement diffuser

What is 40 fpm?

200

This is one major source of noise generation in a Terminal Unit.

What is the Primary Air Damper OR Fan Assembly?

200

This main feature can be found in the Ultrasuite (but not the Ultrasuite with no light system)

What is LED lights

300

This model can be curved concave/convex.

What is LBM or CF?

300

These silencer characteristics should match ductwork.

What is material, gauge (thickness) and dimensions?

300

This is the ventilation effectiveness for displacement.

What is 1.2?

300

This is the difference between duct Total Pressure and Static Pressure, and is measured by Cross Flow Sensors.

What is Velocity Pressure?

300

This motor program is used when a fan filter unit is ducted and there is an upstream VAV device

What is the Constant Torque motor program?

400

This is percentage the throw will reduce by if there is no coanda effect?

What is 30%?

400

The installed pressure drop of silencers is typically this much higher than catalogue data.

What is 2-4x?

400

These are a recommended method of providing heating in an underfloor or displacement application to avoid airflow disruptions 

What are radiant panels, fin tube enclosures, or natural convective heaters (Also accepted RPMs, RPLs, LEs, DLEs, LNTs) perimeter heat?

400

These are the two paths noise can travel to escape from a terminal unit.

What are 1) Radiated Noise and 2) Discharge Noise?

400

The Ultrasuite with no HEPA has a minimum plenum height as low as this number

What is 10"?

500

This is the type of diffuser least impacted by poor inlet conditions.

What is SCD/SPD/Radial Diffuser?

500

This is the latest test standard for silencers with tighter tolerances.

What is ASTM E477-20?

500

Recommended UFAD plenum pressure.

What is 0.05?

500

This is typically the MINIMUM differential pressure of a Cross Flow sensors that can be used for a reliable flow rate measurement.

What is 0.02 in w.g.?

500

The BFC-ST can be ordered in AIO with this model code

What is FFUCS?