407C
410A
Pressure
Refrigerants
Components
100

407c is a binary blend true or false?

False

100

R410A is also Called

Suva, AZ 20, Puron

100

Compression Ratio is?

Absolute discharge pressure divided by absolute suction pressure

100

R410A Tank is colored

Rose

100

The Compressor internal pressure relief (IPR) for R410A systems are set at?

550-625psig

200

What makes 407c like 410A

Its ability to fractionate

200

R410A was invented and Patented by?

Allied Signal now known as Honeywell

200

The Low Pressure control for R410A system will open at?

50psig

200

Subcooled liguid in the reciever will_______depending on the surroundings

Lose or gain subcooling

200

Evaporator or Indoor coil should be______when changing out an existing R22 system.

Replaced with a Coil that meets UL standard of 235psig

300

What is the boiling point for R407C

-43.8

300

R410A contains Flourine, True or False

True

300

Because of its higher vapor heat capacity, discharge temp is_____than R22

Lower

300

When a blend is zeotropic, or near-zeotropic it should be?

Transferred from cylinders as a liquid

300

The flow area of a R410A metering device is...

Smaller than that of R22 metering device.

400

What was R407C intended for?

Replace R22

400

Why cant R410A be used in R22 systems

40%-70% higher Pressures

400

Liguid line Filter Drier for R410A needs to be rated for?

600psig

400

The closer a blend comes to being a true azeotrope...

the less temperature glide it will have.

400

To charge a R410A system you should______to not damage the compressor?

Throttle refrigerant in to the low side.

500

What is the formula make up of R407C

R32 (23%), R125 (25%), R134A (52%)

500

The Boiling point of R410A is?

-48.5

500

R410A System use high pressure switch that will open at?

600psig plus or minus 10psig

500

When Charging a R410A system that uses a capillary tube metering device, the proper charge can be calculated by?

Superheat

500

To remove moisture from Polyol Ester lubricant you should...

Change the filter drier and evacuate to 500 microns