NEC NAVIGATION
CONDUCTORS & AMPACITY
OVERCURRENT PROTECTION
Grounding and Bonding
CALCULATIONS & LOADS
100

Which NEC chapters apply to all electrical installations unless modified?

Chapters 1 through 4 📘 NEC 90.3

100

What table is used to determine allowable ampacity of insulated conductors?

Table 310.15(B)(16)
📘 NEC 310.15(B)(16)

100

What NEC article covers overcurrent protection?

 Article 240
📘 NEC Article 240

100

What NEC article governs grounding and bonding?

Article 250
📘 NEC Article 250

100

How many volt-amperes are calculated per general-use receptacle?

180 VA
📘 NEC 220.14(I)

200

Where are definitions of NEC terms located?

: Article 100

200

What conductor temperature rating is normally used for circuits 100A or less unless otherwise marked?

60°C
📘 NEC 110.14(C)(1)(a)

200

What is the maximum standard breaker size for a #12 copper conductor?

20 amperes
📘 NEC 240.4(D)(5)

200

What is the purpose of bonding?

To establish an effective ground-fault current path
📘 NEC 250.4(A)(5)

200

What is the general lighting load per square foot for a dwelling unit?

3 VA per square foot
📘 NEC 220.12

300

Which chapter contains special occupancies such as hazardous locations and health care facilities?

Chapter 5
📘 NEC 90.3

300

What adjustment factor applies when 4–6 current-carrying conductors are in a raceway?

80%
📘 NEC 310.15(B)(3)(a)

300

When conductor ampacity does not match a standard OCPD size, what rule allows rounding up?

Next higher standard rating
📘 NEC 240.4(B)

300

What table is used to size equipment grounding conductors?

Table 250.122
📘 NEC Table 250.122

300

What demand factor applies to the first 3,000 VA of dwelling lighting load?

100%
📘 NEC 220.42

400

Which NEC article covers grounding and bonding requirements?

Article 250
📘 NEC Article 250

400

After adjustment and correction factors are applied, the conductor ampacity shall not be less than what value?

The load served
📘 NEC 310.15(A)(2)

400

Overcurrent devices shall not be installed where ambient temperature exceeds what value unless listed for the condition?

40°C (104°F)
📘 NEC 240.6

400

What electrode is required at every building supplied by a feeder or service?

Grounding electrode system
📘 NEC 250.50

400

What percentage is used for continuous loads when sizing conductors and OCPD?

125%
📘 NEC 210.20(A), 215.3

500

Q: Which NEC chapter contains communications systems and does not generally apply to power wiring rules?

Chapter 8
📘 NEC 90.3

500

A #12 THHN conductor at 90°C is adjusted for 6 current-carrying conductors. What is the adjusted ampacity before termination limits?

30A × 80% = 24A
📘 NEC 310.15(B)(16), 310.15(B)(3)(a)

500

A 65A calculated load is served by a conductor rated 70A. What is the maximum breaker allowed?

70 amperes
📘 NEC 240.4(B), 240.6

500

What is the minimum size copper grounding electrode conductor to a single rod electrode?

#6 AWG copper
📘 NEC 250.66(A)

500

A 240V motor draws 28A continuous. What is the minimum conductor ampacity required?

35 amperes
📘 NEC 430.22(A)