Trees and landscaped areas around the perimeter of the building SHALL be maintained to prevent Blank or Blank
Blind spots or Access to roof
How should signs be attached to a fire door?
Where should they be attached?
With an adhesive.
Signs shall not be installed on glazing in fire doors.
Signs shall not be installed on the surface of fire doors in such a way that impairs or otherwise interferes with the proper operation of the fire door
Fencing at play areas and athletic fields need how many gates and for what?
At least two gates, one for egress, one for service equipment.
When are manual door stops allowed?
Only for use on exterior doors or non fire rated or smoke rated doors.
How high does the fence have to be that separates kindergarten and daycare play areas?
4 feet
The total area of all attached signs shall comply with the following:
(1)
Signage comprising combustible materials shall not exceed ? percent of the area of the face of the fire door.
(2)
Signage that is painted on with stencils or other similar methods shall not be limited in area.
(3)
Vinyl signage up to 0.008 in. (0.2 mm) in thickness shall not exceed ? percent of the area of the face of the fire door
The total area of all attached signs shall comply with the following:
(1)
Signage comprising combustible materials shall not exceed 5 percent of the area of the face of the fire door.
(2)
Signage that is painted on with stencils or other similar methods shall not be limited in area.
(3)
Vinyl signage up to 0.008 in. (0.2 mm) in thickness shall not exceed 5 percent of the area of the face of the fire door.
(4)
Metal signage up to 20 gauge thickness shall not exceed 200 in.2 (0.13 m2).
Walls, railings, or other physical barriers SHALL be used to define and protect any vertical drop of how many inches?
18 inches
When are emergency windows required?
What are their requirements for operation?
(f) Emergency Rescue Openings (Secondary Means of Egress).
1. In non-sprinklered buildings, every instructional space, and other spaces normally subject to student occupancy of 10 or more, shall have at least 1 window, panel, or door leading to the exterior or to a separate atmosphere.
In buildings equipped with an approved automatic sprinkler system, emergency access openings shall be spaced not more than 200 lineal feet apart.
For buildings designed after October 18, 1994, the emergency rescue opening shall be provided in rooms over 250 square feet used for classroom or other educational purposes or normally subject to student occupancy of 6 or more.
Windows and panels shall be operable from the inside by a single operation and without the use of tools.
What is the required illumination in candles for the following areas?
Parking
Covered and connector walks
Parking entrances/exits
Parking-1ft candle
Covered and connector walks-1ft candle
Parking entrance/exit-2ft candle
Gap Allowances for Fire Doors made of Wood:
Gap Allowances for Fire Doors made of Steel?
Wood