100

Length of a hydrostatic test to be performed on a reconstructed tank or a tank that has undergone major repairs

What is 24 hours?

100

Method to repair an External Floating Roof

What is any method?

API-653 3rd edition Addendum 3 Section 9.12.1 External Floating Roofs states "Any method of repair is acceptable that will restore the roof to a condition enabling it to perform as required."

100

The area on a tank bottom where settlement begins.

What is Breakover Point?

100

Friday's appropriate office attire

What is Hawaiian shirts?

200

Minimum dimension for a replacement shell plate

What is 12 in. or 12 times the replacement plate thickness, whichever is greater?

API-653 3rd edition Addendum 3 Paragraph 9.2.2.1 states "The minimum dimension for a replacement shell plate is 12 in. or 12 times the thickness of the replacement plate, whichever is greater."

200

T/F: Internal and external pontoon roofs must meet the same punctured design conditions

What is True?

See API-650 11th Edition Paragraphs C.3.4.1 & H.4.2.1.3

200

Record which establishes the validity of a WPS

What is a PQR (Procedure Qualification Record)?

200

"Where the money is at" in TI

What is Crude Oil?

Source: Brian

300

To use UT in lieu of RT to test tank construction welds, you follow this

What is API-650 Annex U?

300

Type of roof centering device


What is a Bazooka?

300

A set of steps over a dike wall or piping run that provides access from one side to the other.

Typically follows the contour of the dike wall up and over to the other side or simply spans the distance across ground-based piping around a tank.

What is a Stile?

300

Steve's undergrad school

What is Virginia Tech?

400

Distance where a welded-on patch plate shall be tombstone shaped

What is within 6 in. from the shell?

API-653 3rd Ed. Addenudum 3 Section 9.10.1.2 states "When a welded-on patch plate is within 6 in. of the shell, the welded-on patch plate shall be tombstone shaped."

400

A type of seal on an internal floating roof where a secondary seal is not required

What is a Liquid-Mounted Seal?

"Under current EPA regulations, internal floating roofs equipped with liquid-mounted seals are not required to have secondary seals."

400

The process by which corrosion rates and inspection intervals are established for a candidate tank using corrosion rates and service history from a control tank for the purpose of establishing the next inspection date

What is Similar Service Assessment?

400

Number of employees on the TI team

What is 13?

500

Equation for calculating the limiting stress within a repair area on the shell of a tank, which shall not exceed 7000 lbf/in^2.

S = (2.6 H D G)/t

where:

S = shell stress in lbf/in.2, 

H = tank fill height above the bottom of repair or alteration in ft, 

t = shell thickness at area of interest in in., D = tank mean diameter in ft, 

G = specific gravity of product.

API-653 3rd Ed. Paragraph 12.3.2.3.3

500

Minimum thickness of new roof plates on a supported cone roof

What is 3/16" plus any corrosion allowance as specified in the repair specifications?

500

Inspection technique intended to locate and monitor emissions sources from tank defects in the welds or plate surfaces of the structure by analyzing ultrasonic stress waves that are released when the material deforms under stress.
Relatively newer.

What is AE (Acoustic Emission Testing)?