100

Termination provisions of equipment for circuits rated 100 amperes or less, or marked for 14 AWG through 1 AWG conductors, shall be rated _____ degree column.

What is 60 degree?

110.14(C)(1)(a)(1)

100

Flexible Metal Conduit (FMC) must be secured within _____ of each box, cabinet, conduit body or other termination.

What is 12 in?

348.30(A)

100

What article will you find definitions?

What is Article 100?

100

A flexible cord is permitted for an in-sink waste disposal if the cord length is no longer than?

What is 36in?

422.16(B)(1)(1)

100

The maximum approval electrical trade size of IMC is ________

What is 4 inch?

342.20(B)

200

The minimum feeder conductor ampacity shall be no less than the noncontinuous load plus ____ percent of the continuous load and not less than the maximum load after the application of adjustment and correction factors.

What is 125%?

210.2(A)(1)(a)


200

Grounding type receptacles shall be used on which of the following branch circuits.

What is 15- and 20- Ampere?

406.4(A)

200

The conductors between the service equipment, a separately derived system, or other power supply and the final branch circuit overcurrent device:

What is Feeders?

Article 100

200

Receptacles not supplying loads directly related to circulation systems must be located not less than _____ from the inside walls of the pool?

What is 6ft?

680.22(A)(2)


200

_____ is the maximum approved electrical trade size for PVC conduit.

What is 6in?

352.20(B)

300

The ampacity adjustment factors don’t apply to conductors installed in surface metal raceways if the cross sectional area of the raceway exceeds ______?

What is 4in?

486.22(1)

300

Maximum allowable ampacity for 10 AWG copper conductor is _______ in the 60 degree Column.

What is 30 Amperes?

Table 310.16

300

Load where the maximum current is expected to exist for ______ hours or more is termed as continuous load:

What is 3 Hours?

Article 100

300

For equipment rated 800 A or more, personal doors located less than _____ from the nearest edge of the working space must open in the direction of egress and have listed panic hardware:

What is 25 ft?

110.26(C)(3)

300

The largest amount of current capable of being delivered at a point on the system during short circuit condition.

What is Fault Current, Available?

Article 100

400

The Adjustment factor for 18 #12THWN current carrying conductor in 1" PVC in a 20" raceway is:

What is None?

310.15(C)(1)(b)

Raceway does not exceed 24"

400

The overcurrent protection device of non-motor appliances must not exceed ________ if the overcurrent device rating is not marked?

What is 20 amperes?

422.11(E)(2)

400

A point on the wiring system at which current is taken to supply Utilization equipment.

What is outlet?

Article 100

400

The total rating of a cord and plug connected room air conditioner must not exceed ______ of the rating of a branch circuit where lighting outlets, other appliances, or general use receptacles are also supplied?

What is 50%?

440.62(C)

400

Maximum distance to any receptacles shall be ______ along the floor line of any wall space measured horizontally?

What is 6 ft?

210.52(A)(1)

500

For a 1" conduit making a straight pull thru a box, what size box would you need?

Code article?

What is 8"?

314.28(A)(1)

500

Service drop conductors shall have ____.

(a) sufficient ampacity to carry the load.

(b) adequate mechanical strength.

(c)sufficient ampacity to carry the load or adequate mechanical strength.

(d) sufficient ampacity to carry the load and adequate mechanical strength.

(d) sufficient ampacity to carry the load and adequate mechanical strength.

230.23(A)

500

The conductors from the service point to the service disconnecting means.

What is Service Conductors?

Article 100

500

If internal combustion engines are used as the prime mover, an onsite fuel supply must be provided for not less than ______ of full demand operation of the system?

What is 2 hours?

701.12(D)(2)

500

Maximum overcurrent protection for 12 AWG copper conductor is?

What is 20 amperes?

240.4(D)(5)