In which chapter would you find the article “Outside Branch-Circuits and Feeders” ? 

Extra Points-

What article is “Outside Branch-Circuits and Feeders”?

What is Chapter 2?

Extra-

What is Article 215?

100

 Intermittent operation of electrical equipment in which the load conditions are regularly recurrent is called?

What is Duty, Periodic?

Article 100

100

A building or structure supplied by a feeder shall have _____ installed

a grounding electrode system

250.32(A)

100

The ampacity of of UF cable shall be that of ___ conductors in accordance with 310.14.

What is 60 degrees?

340.80

200

When does a branch circuit extension NOT require AFCI protection?

if less than 6ft AND no devices are added. 

210.12(D) Exception

200

The conductors from the service point to the service disconnecting means.

What is Service Conductors?

Article 100

200

The grounding ring shall be installed not less than  ____ below the surface of the earth?

What is 30in.

250.53(F)

200

_____ is the maximum approved electrical trade size for PVC conduit.

What is 6in?

352.20(B)

300

A receptacle must be located within ____ft of an air conditioner

25

210.63

300

A device, or group of devices, or other means by which the conductors of a circuit can be disconnected from their source of supply.                

What is Disconnecting Means?

Article 100

300

What minimum size copper bond wire is needed for equipotential bonding of pool equipment?

#8 solid

680.26(B)

300

What is the max distance for supports on a 3" PVC pipe?

What is 6 ft

Table 352.30

400

The minimum size copper ground for a 100 Amp circuit

8AWG

Table 250.122

400

An enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung

Cabinet

Article 100

400

Equipment Grounding Conductors can be taped green at the time of installation at every accessible point, IF ____AWG or larger

4

250.119(A)

400

The maximum approval electrical trade size of IMC is ________?

What is 4 inch?

342.20(B)

500

According to the NEC®, which MINIMUM enclosure type letter would be required where the _____
installation is a motor controller located outdoors, in an area that is subject to heavy rain and snow?

Type 3

Table 110.28

500

The largest amount of current capable of being delivered at a point on the system during short circuit condition.

What is Fault Current, Available?

Article 100

500

A concrete encased electrode shall be a bare copper conductor not smaller than____?

What is #4

250.52(3)(2)

500

True or False

Is ENT approved for direct burial?

False.

362.12 (4)