condensate polisher
regen system
waste recovery
SGBD system and Demin water
could be anything
100

with the auto A closed and the auto E closed the DMV is in this status

Out of service

100

leaving anion resin behind in the CRV can result in this condition. 

none.  sulfate form anion resin does not affect steam generator chemistry unless influent pH is very high.

100

with a conductivity of 392 uS/cm low conductivity waste will be diverted to 

the raw water basin

100

a high level in the SGB flash tank results in this condition

A high level dump to the condenser.

100

when operating a component, ensuring the correct system response is the 

"R" in STAR

200

During power ascension @ 50% power and with a polisher D/P of 59 PSID you must________

place another DMV in service

200

the CRV and M&H vessels both have a ____ ____

false floor

200

The waste recovery system is powered by this group bus. 

"H" bus

200

the maximum level in the DM water storage tanks is 

90%

200

Don's favorite band from the 90's who lost their lead singer to a drug overdose was

Alice in Chains

300

2 circulators have tripped due to grassing and condensate temperatures have increased to 138 deg F.  this action must be taken in regards to the condensate polisher. 

none

300

Failure to ensure Lh flow through the Th during rinses could result in this condition. 

create a salt shaker if performing a full regen. 

300

having a build up of iron on the WRS quartz filter can help mitigate

high TRC at the NRW basin

300

This method of operation used when transferring resin from a SGBD demin mixed bed to a dumpster

manual operation of the system

300

the scariest thing in the plant according to Don is

a steam leak

400

the CN108s will automatically open when this condition occurs.  

none. there is no automatic function of the CN108 valves

400

when performing manual operations of a regen, the system will not provide this function

trip

400

All WRS valve switches must be in this position for the system to operate in automatic

Auto

400

the Demineralized Water Storge Tanks (DWST) can hold this amount of water each

500,000 gallons

400

____________ is the G.O.A.T band of Heavy metal 

Black Sabbath

500

With DMV flow rates at 3000 GPM an operator should take this action

take a DMV to stand-by to increase flow rates across the remaining DMVs and prevent channeling.  

500

with a low level in the low pit alarm locked in the regen system will 

not trip

500

this valve is used to throttle flow through the WRS (if desired)..

2CP181

500

with the 2GB217 closed blowdown flow is directed to

the SGBD system and then to 23 condenser

500

A good operator uses these when operating plant equipment

4  of their 5 senses.  sight, hearing, smell, and  touch.  not taste unless you want to..... i wouldn't