Substitutions
#Receptacles
Pictures
Earth
Keep it Light
100

The alternative replacement breaker for a Siemens

What is an Eaton CL?

100

The smallest kitchen counter space required to have a receptacle installed. 

12 inches

210.52(C)(1)

100

Is this a standard size breaker according to the NEC

No

Table 240.6(A)

100

A separate building does not require a grounding system when _______. 

The building is fed with only a single branch circuit. 

250.32(A) Exception

Note: this exception does not apply to a Feeder. 

Read definitions of feeder and branch circuit

100

What’s an electrician’s favorite ice cream flavor?

Shock-o-late

200

The alternative replacement breaker for a Square D Homline

What is an Eaton CL?

200

The amount of receptacles required in a dwelling unit garage. 

1 per vehicle bay

210.52(G)(1)

200

Is this installation NEC compliant?


No

240.81

200

What minimum size copper bond wire is needed for equipotential bonding of pool equipment?

#8 solid

680.26(B)

200

Which is an electrician's favorite band?

AC/DC

300

The alternative replacement breaker for a Challanger

What is an Eaton BR?

300

A receptacle must be located within ____ft of an air conditioner

25

210.63

300

The wire size and breaker size you would use for this AC unit.


#10 Copper

50A Breaker

440.4(B)

300

Flexible Metal Conduit can be used as the equipment grounding conductor if the circuit is _____Amps or less

20

250.118 Note other requirements that must also be met

300

Where do electricians get their supplies?

The Ohm Depot

400

The alternative replacement breaker for a Square D QO

What is an Eaton CHQ?

400

Bathroom lights cannot be installed with bathroom receptacles. True or False

False. If the parameters are met

210.11(C)(3) and Exception

400

What is the maximum distance

30

550.32(A)

400

Equipment Grounding Conductors can be taped green at the time of installation at every accessible point, IF ____AWG or larger

4

250.119(A)

400

Where was the electrician so excited to go shopping with his wife?

To the outlet mall.

500

The alternative replacement breaker for a Bryant

What is an Eaton BR?

500

When does a branch circuit extension NOT require AFCI protection?

if less than 6ft AND no devices are added. 

210.12(D) Exception

500

The minimum distance needed above the tub

8ft

410.10(D)(1)

500

What system or material is not permitted for use as a Grounding electrode. 

there are multiple answers

1. Metal underground gas piping systems

2. Aluminum

3. The structures and structural reinforcing steel described in 680.21(B)(1) and (B)(2)

250.50(B)

500

What do you say when you break up with an electrician?

Watt is love?

Baby don't hertz me.

Don't hertz me.

N-ohm-ore.

N-ohm-ore.