Depth of working space in front of a panel shall be a minimum of ____.
36"
110.26(A)(1)
There shall not be more than ______ degrees total between pull points of a run of PVC
360
352.26
When are cables allowed to support other cables?
Never
300.11(D)
The panel circuit directory shall include an approved degree of detail that allows each circuit to be _______________________.
distinguished from all others.
408.4(A)
A High-Leg in a three phase delta system must have an outer finish that is _____ in color...
Orange
110.15
True or False?
Luminaires are permitted to be installed on trees
True
410.36(G)
What is the minimum distance from the bottom of the service disconnect for a mobile home to the finished grade?
2ft
550.32(F)
When adjusting ampacity for more than three current carrying conductors in a raceway, what is the adjustment factor for 6 conductors?
80%
310.15(C)(1)
NM cable cannot be installed in wet locations. Is it permitted to be in a raceway that is installed outdoors?
NO
300.9
Where a cable or raceway is installed through bored holes in joists, the edge of the hole shall not be less than ____ from the nearest edge of the wood.
1.25"
if this cannot be maintained the cable shall be protected by steel plates
300.4(A)(1)
True or False?
EMT is permitted to be used for the support of luminaires
False
358.12(2)
In what condition is a raceway required to be sealed? (duct seal)
when portions of a raceway are subjected to different temperatures
300.7(A)
Which is the only orientation that a panelboard is prohibited from being installed in?
Face-up
408.43
NEC requires vending machines rated 150v to ground or less, 60a or less, to have what kind of protection?
Class A GFCI protection for personnel
422.5(A)(5)
True or False?
LFNC (seal-tight) is permitted to be installed in lengths longer than 6'
True
356.10(5)
Outlets supplying all pool motors rated _____amps or less shall be provided with Class A GFCI protection
60
680.21(C)
what is the minimum clearance for recessed led luminaires to the nearest point of clothes closet storage space?
6"
410.16(C)(3)
Which Code section is this violation illustrating?
230.7
When making a splice in a J-box with conductors 4 AWG or larger, the distance between the raceway entry and the opposite wall of the box shall not be less than ____ times the size of the largest raceway in a row.
6
314.28(A)(2)
The number of conductors is limited to fill the conduit to what percentage when 2 or more conductors are installed?
40%
Chapter 9, Table 1
352.22
*Note 4 does allow up to 60% fill when the raceway is not longer than 24"