Enter Category
Enter Category
Enter Category
Enter Category
Enter Category
100

The following is a function of an expansion device: ____.


a.

produce a reduction in the pressure on the liquid refrigerant


b.

regulate the flow of refrigerant into the evaporator


c.

lower the boiling point of the refrigerant far enough below the temperature of the load to get the needed heat transfer rate


d.

All of the above.

D

100

When the load on the evaporator increases, the TXV ____.


a.

increases the flow of refrigerant


b.

decreases the flow of refrigerant


c.

maintains constant head pressure


d.

decreases the pressure drop across the evaporator

a.

increases the flow of refrigerant

100

The purpose of a capillary tube is to ____.


a.

regulate the refrigerant flow into the evaporator


b.

lower the pressure of the liquid refrigerant


c.

lower the boiling point of the refrigerant


d.

All of the above.

All of the above.

100

The pin or valve port piston of the electronic step-motor expansion valve can move in a linear motion of 0.0000783 in./step.


a.

True


b.

False

TRUE

100

The TXV maintains a constant ____________________ in the evaporator.

SUPERHEAT

200

A thermostatic expansion valve meters refrigerant flow to the evaporator based on the ____.


a.

rate of liquid vaporization


b.

evaporator suction line superheat


c.

external equalizer pressure


d.

All of the above.

evaporator suction line superheat

200

If the thermal bulb assembly develops a leak, what will occur?


a.

All of the system's refrigerant will leak out.


b.

The bulb pressure will reduce and the valve will close.


c.

The valve will open to allow more refrigerant to flow.


d.

It will have no effect on system operation.

B)The bulb pressure will reduce and the valve will close.

200

Pressure entering the compressor that is too high will cause the density of suction gases entering the compressor to increase.


a.

True


b.

False

TRUE

200

An automatic expansion valve uses a thermal bulb to help control the amount of refrigerant being fed into the evaporator.


a.

True


b.

False

FALSE

200

As the evaporator load increases, an automatic expansion valve will ____________________ to maintain the suction pressure at the set point.

CLOSE

300

If a thermostatic expansion valve's thermal bulb came loose from the suction line at the outlet of the evaporator, which of the following could result?


a.

The bulb pressure would increase and the thermostatic expansion valve would open.


b.

The superheat in the evaporator would decrease.


c.

The evaporating pressure and the compressor’s suction pressure would increase.


d.

All of the above are correct.

D

300

The purpose of an external equalizer in a TXV is to ____.


a.

compensate for excessive evaporator pressure drop


b.

allow system to equalize faster


c.

prevent the expansion valve from frosting up


d.

allow refrigerant to expand in the compressor

a.

compensate for excessive evaporator pressure drop

300

The pressure-limiting TXV is desirable in low temperature applications because it keeps the suction pressure to the compressor down during hot pulldowns.


a.

True


b.

False

TRUE

300

When the evaporator pressure drops, the automatic expansion valve will open to allow more refrigerant to enter the evaporator.


a.

True


b.

False

TRUE

300

The two pressures that push to close a thermostatic expansion valve are the ____________________ pressure and the evaporator pressure.

SPRING

400

The TXV sensing bulb is mounted ____.

a.

on the liquid line between the condenser and the TXV

b.

at the inlet to the condenser

c.

on the suction line between the evaporator and the compressor

d.

on the compressor discharge line




C) on the suction line between the evaporator and the compressor

400

Balanced port TXVs are used to ____ ambient temperatures.


a.

feed refrigerant at a normal rate with low


b.

feed refrigerant at a normal rate with high


c.

stop refrigerant flow with high


d.

stop refrigerant flow with low

A) feed refrigerant at a normal rate with low

400

The solid-state controlled step-motor valve has a temperature sensor, or thermistor, as one of its inputs.


a.

True


b.

False

TRUE

400

AXVs are usually found on smaller equipment with somewhat constant evaporator loads.


a.

True


b.

False

TRUE

400

The automatic expansion valve maintains a constant ____________________ in the evaporator

PRESSURE

500

The cross liquid charge bulb at the TXV contains fluid that ____.


a.

has similar characteristics to the system fluid to prevent liquid refrigerant from entering the suction line


b.

has different characteristics from the system fluid


c.

causes the valve to stay open during the off cycle


d.

follows the system’s pressure-temperature relationship


b.

has different characteristics from the system fluid

500

The pressure-limiting TXV ____.


a.

allows the compressor to operate at low condenser entering air temperatures


b.

shuts off the condenser fan during hot pull down


c.

maintains the full refrigerant flow rate during a hot pulldown


d.

keeps the suction pressure to the compressor down during a hot pulldown

d.

keeps the suction pressure to the compressor down during a hot pulldown

500

The step-motor valve uses a small motor to control the valve's port, which in turn controls evaporator superheat.


a.

True


b.

False

TRUE

500

A capillary tube metering device controls the refrigerant flow by pressure drop.


a.

True


b.

False

TRUE

500

Why should the TXV be adjusted to maintain a low superheat?

To ensure that the majority of the evaporator surface is being used, giving a higher net refrigeration effect and higher capacities and efficiencies.