Administration
Fixtures
Water Distribution
Drainage
Traps
100

This document shall be known as the _____.

(A) Uniform Plumbing Code (C) National Plumbing Code

(B) Universal Plumbing Code (D) World Plumbing Code

A 101.1

100

Fixtures having concealed slip-joint connections shall be provided with _____.

(A) a utility space or access panel (C) red brass fittings

(B) a ladder and a light fixture (D) rubber gaskets

A 402.10

100

The code requirement for “an adequate supply of potable running water” is for _____.

(A) cleansing and sanitation (C) water-cooled equipment

(B) protection of trap seals (D) hydronic systems

A 601.2

100

Except for plastic pipe, in lieu of a water test, drainage piping may be tested with _____.

(A) air (C) smoke

(B) ether (D) gas

A 712.1

100

Each fixture trap shall have a liquid seal of _____.

(A) not less than 2 inches (C) both A and B

(B) not more than 4 inches (D) none of the above

C 1005.1

200

When the requirements within the jurisdiction of this plumbing code conflict with the requirements of the

mechanical code, _____ shall prevail.

(A) the Mechanical Code (C) the Building Code

(B) this code (D) either code

B 102.1

200

Trough urinals shall be _____.

(A) permissible if constructed of concrete (C) prohibited

(B) required in large associations (D) allowed in bus stations

C 405.2

200

Ballcocks in water closet tanks shall be installed so that the critical level of the water inlet is above the full opening of the overflow pipe of not less than _____.

(A) 1/2 inch (C) 3 inches

(B) 1 inch (D) 6 inches

B 603.5.2 and

Table 603.2

200

The acceptable fitting for connecting a horizontal drain line with another horizontal drain line is a _____.

(A) sanitary tee (C) combination wye and 1/8 bend

(B) cross tee (D) side inlet 1/4 bend

C 706.3

200

One trap may serve a set of not more than _____ single compartment sinks.

(A) two (C) three

(B) one (D) four

C 1001.2

300

To obtain a permit, the applicant shall first file _____ therefore in writing on a form furnished by the Authority Having Jurisdiction for that purpose.

(A) a request (C) an application

(B) for permission (D) plans

C 104.3

300

The minimum distance from a side wall or partition to the center of a urinal shall be _____ inches.

(A) 6 (C) 18

(B) 12 (D) 24

B 402.5

300

After allowing for friction and other pressure losses, the residual water pressure shall be at least _____.

(A) .433 psi (C) 15 psi

(B) 7.5 psi (D) 29 psi

C 608.1

300

The maximum trap loading for a 3 inch trap is _____.

(A) one unit (C) four units

(B) three units (D) six units

D Table

702.2(1)

300

Floor drains shall connect into a trap so constructed that it can be _____.

(A) accessible (C) readily cleaned

(B) easily removed (D) none of the above

C 1006.1

400

This code is an ordinance to provide _____ for the protection of the public health, safety, and welfare.(A) guidelines 

(B) maximum requirements and standards 

(C) suggested ways of installation

(D) minimum requirements and standards

D 101.3

400

The water supply to a bathtub and whirlpool bathtub filler valve shall be protected by an _____ .

(A) air break (C) ASSE 1017

(B) air gap (D) ASSE 1070

B 409.5

400

The quantity of water required to be supplied to every plumbing fixture shall be represented by _____.

(A) gallons per minute (C) fixture units

(B) feet per second (D) available head pressure

C 610.3

400

A domestic dishwasher, with independent drain, has a drainage fixture unit value of _____.

(A) 2 (C) 4

(B) 3 (D) 1

A Table 702.1

400

Each building trap when installed shall be provided with _____.

(A) a cleanout

(B) a relieving vent or fresh air intake on the inlet side of the trap

(C) both A and B

(D) none of the above

C 1008.1

500

Temporary connection of the plumbing equipment to the source of energy or fuel for the purpose of testing_____.                                                     (A) is not allowed unless the inspector is present   (B) shall be permitted to be authorized by the Authority Having Jurisdiction                                 (C) is not allowed unless the equipment has been inspected and approved                                      (D) is not allowed under any circumstances

B 105.4

500

The path of travel to an emergency eyewash shall be _____.

(A) clearly identified (C) no more than 50 feet

(B) in a straight line (D) no more than 100 feet

A 416.4

500

A type of plastic water piping that may be tested with air is _____.

(A) PVC (C) PE

(B) CPVC (D) PEX

D 609.4

500

Dual sewage ejectors for public use require _____ alarm.

(A) audio (C) visual

(B) audio and visual (D) audio or visual

B 710.9

500

The developed length of a 2” trap arm, from the trap weir to the inner edge of the vent shall not exceed

_____ feet.

(A) 3 (C) 6

(B) 5 (D) 10

B 1002.2 and

Table 1002.2