Year 1 Rocks!
Math is Everywhere!
Know the Code
Potpourri
Math is Da-Bomb
100

34.  If the resistance is raised in a simple circuit, what will the current do?

a. Remain the same

b. Go up

c. Fluctuate

d. Go down

What is go down?

(d.)

100

17.  A 1,000 watt heating element will draw ____ amps at 120 volts.  The element is rated to operate at 120 volts.

a. 6.67

b. 10.41

c. 14.4

d. 8.33

What is 14.4 amps?

(d.)

100

11.  Grounding is covered in Article ____ in the NEC.

a. 110

b. 250

c. 210

d. 200

What is Article 250?

(b.)   NEC 250.1

100

39.  If three 2" x 3" sectional boxes are fastened together properly, what is the resulting combination called?

a. 3-way box

b. 3-switch box

c. 3-gang box

d. 3- position box

What is 3-gang box?

(c.)

100

21.  If you use 25% of the conduit from the storage rack, how many feet of conduit will you have remaining on the rack?  You started with 580 sticks of pipe that are each 10 feet long.

a. 435

b. 1450

c. 232

d. 4350

e. 2320

What is 4350 feet?

(d.)

580 X 10 = 5800

5800 x (100%-25%) = 4350 ft.

200

42.  What does the "Sp" symbol represent?

a. switch with pilot lamp

b. power switch

c. perimeter switch

d. pull chain switch

What is a switch with pilot lamp?

(a.)

200

66.  To feed a 240-volt resistive heating load that draws 10 amps, 400' of raceway is installed.  You pulled in 12 AWG THHN copper conductors.  Where K=12, what is the voltage drop on the wire?

a. 29.4

b. 9.25

c. 8.49

d. 14.7

e. 7.35

What is 14.7?

(d.)

200

57.  What is the ampacity of 10 AWG THWN/THHN copper wire in a 63oC environment?

a.  26 A

b. 30 A

c. 11.55 A

d. 40 A

e. 35 A

What is 26 A?

(a.)

Table 310.15(B)(16)/310.15(B)(2)

200

47.  To get a 40-inch long 90o stub-up in 1 1/4-inch EMT, you will place the bender arrow at ____ inches from the measured end of the conduit.

a. 32

b. 31

c. 30

d. 29

e. none of these

What is 29 inches?

(d.)

200

36.  A duct heater has a nameplate rating of 6.32KW @ 250 volts.  This duct heater will draw ___ amperes, when operated at 230 volts.

a. 25.28

b. 27.48

c. 9.89

d. 23.26

e. 29.87

What is 23.26?

(d.)

300

52.  In a dry location, the maximum operating temperature of a conductor with Type THHN insulation is ____ oC.

a. 60

b. 75

c. 90

d. 105

What is 90oC?

(c.)

300

119.  A room is to be illuminated with track lighting.  Twenty track heads (fixtures) will be installed in the track.  A 75 W PAR38 lamp will be installed in each head.  The lighting is to be controlled by a dimmer.  The smallest dimmer that can be installed has a rating of ___ watts.

a. 600

b. 1,000

c. 1,500

d. 2,000

What is 1,500 watts?

(c.)

20 x 75W = 1,500 W

300

71.  The Code section that addresses sensor (automatic) control of lighting in a restaurant bathroom is ___.  Select N/A (not applicable) if there is NOT a Code reference for this.

a. 210.20(A)(1) Exc 2

b. 210.8(A)(1)

c. 210.8(B)(1)

d. 210.70(A)(2)

e. N/A

What is N/A?

NEC 210.70(A)(1) Exc 2

300

102.  Luminaire is a term that refers to ________.

a. incandescent lighting fixtures

b. fluorescent lighting fixtures

c. outdoor pole-mounted fixtures

d. either a or b

e. either a, or b, or c

What is either a, or b, or c?

(e.)

300

144.  What is the minimum size EMT required for a new installation where six 1/0 AWG and nine 3/0 AWG THHN/THWN copper conductors are to be installed?

a. 2

b. 2 1/2

c. 3

d. 3 1/2

e. none of these

What is 3?

(c.)

[6 x .1855] + [9 x .2679] = 3.5241 in2 = 3" EMT

400

74.  SPDT switches are commonly called "___-___" switches.

a. three-way

b. single-pole

c. double-pole

d. four-way

What is three-way switches?

(a.)

400

145.  What minimum size Schedule 80 PVC conduit is required where four 600 kcmil and one 1/0 AWG conductors are to be installed?  All conductors are THHN/THWN.

a. 2 1/2

b. 5

c. 6

d. 4

e. 2


What is 4?

(d.)

4(.8676) + 1(.1855) = 3.6559 in2 = 4" PVC

400

84.  For branch circuits rated 120 volts, 20 ampere and supplying two or more receptacles, the receptacles are permitted to be rated _____.

I. 15 amperes

II. 20 amperes

a. I only

b. II only

c. either I or II

d. neither I or II

What is either 15 amperes or 20 amperes?

(c.) either I or II

NEC 210.21(B)(3)

400

62.  NM cable is permitted to be installed in normally ___ locations.

a. wet

b. dry

c. damp

d. any of these

What is dry locations?

(b.)

400

26.  How many complete sections of Wiremold can be cut from a 5-foot-long piece that you remove from the shipping box?  Each section will need to be cut so that it is 1'-2 3/8" long.

a. 3

b. 4

c. 5

d. 6

e. 7


What is 4 sections?

(b.)


500

88.  NEC Section ____ requires that all 125-volt, single-phase 15- and 20-ampere receptacles used for temporary construction power be GFCI protected.

a. 250.138(A) Exception

b. 215.9

c. 210.8(B)

d. 590.6(A)

e. 590.4(D)

What is 590.6(A)?

(d.)

500

35.  What is the current drawn by a garage door opener motor if the nameplate supplies the following information and it is operated at 130 volts:

            13.8 amps              115 amps

a. 8.3333

b. 9.4203

c. 8.6956

d. 13.8

e. 15.6

What is 15.6?

(e.)

500

122.  As measured along the floor line, make sure tht a receptacle is not more than _____ feet from the next receptacle when laying out the wall receptacle locations in a bedroom in a house.

a.  4

b.  6

c.  12

d.  9 

e.  2


What is 12 feet?

(c.)

NEC 210.52(B)(2)

500

129.  In a dwelling, 12-volt thermostat wiring is generally considered to be ____ wiring.

a.  Class 2

b.  Class 3

c.  Class 1

What is Class 2 wiring?

(a.)

500

48.  For a single-family dwelling with a total of 3500 square feet of occupied area, the minimum number of 15-ampere lighting branch circuits is ____.

a. 8

b. 5

c. 7

d. 6


What is 6 circuits?

(d.)