Minimum Depth of Cover
Meter Assembly Components/ AOC's
Structure Over Service
General Knowledge
Improper Vent Clearance
Vehicle Barrier Protection/ Outside & Inside meter clearance violations
100

__________ requires a 24" minimum.

Maryland

100

Identify each part?

1) Regulator 2) Regulator Vent 3) Riser Valve (Stopcock) 4) Meter Nut (Swivel Nut) 

100

Report any SOS to ____________ or your ___________?

Dispatch or your Supervisor

100

Vent terminations shall allow gas to vent freely away from _______, _______, __________ or _________?

Building openings, windows, doors or Air Intakes.

100

from an IRV regulator with an inlet connection larger than 3/4" maintain ________ clearance.

3'

100

4' is the?

Maximum distance between protection posts.

200

Service lines in private property _______ inches.

12

200

Identify each component?

1) Bypass valves 2) Control lines 3) Meter Instrument 4) Meter

200

A Structure Over Service is an?

An Enclosed Dwelling, intended for occupancy, built over an existing service line.

200

All vent terminations shall be a Minimum _________ inches above grade with an _________ resistant screen.

12inches, Insect

200

From an IRV regulator with 3/4" inlet connection maintain ____ clearance.

2'

200

Guards may consist of __________, ________, ______, etc?

Posts, Bollards, Railings 

300

18" for distribution lines in ___________ or ___________?

Streets or Roads

300

Unusual meter sounds may indicate?

The meter is operating abnormally.

300

What is Not an SOS _____, _______, _______, ________, _________________?

Car port, Shed, Porches, Decks & Services & risers originally installed through foundation (older homes with indoor meters)

300

All Vent lines shall terminate ___________________?

Outdoors.

300

Inside meters maintain a minimum of _____ away from sources of ignition or heat that will raise the temperature of the meter above ____F?

3 Feet 120 Degrees Fahrenheit.

400

Refer services not meeting a minimum depth to ___________ ____________?

Corporate Engineering.

400

Rapid meter dial movement may indicate that the ___ is flowing rapidly or a major ____________ is downstream of the meter? 

Gas, Major Leak

400

Additions, Attached / Detached garages & Workshops are known as an?

SOS...

400

Riser valve that is 75% closed requires?

Immediate Action.

400

Outside meters maintain a minimum of ______ away from arc producing equipment or other sources of ignition.

1'

500

If there is No Immediate Hazard. What should you do?

Schedule it for repairs.

500

Meters and piping exposed to traffic must be _____________?

Protected.

500

Pipes connected to valves shall be?

Plugged.