CHAPTER 2
CHAPTER 6
CHAPTER 7
CHAPTER 9
CHAPTER 12
100

THE LENGTH ALONG THE CENTERLINE OF THE PIPE AND FITTINGS IS THE?

DEVELOPED LENGTH 

206.0

100

WHAT IS THE MINIMUM HEIGHT OF A VACUUM BREAKER ON A URINAL?

6"

100

MAXIMUM FIXTURE UNIT LOADING ON A 2" WASTE STACK IS?

16

703.2

100

WHAT IS ONE FACTOR TO DETERMINE THE SIZE OF A VENT PIPE?

LENGTH, FIXTURE UNITS, SEWER SIZE

904.1

100

PLASTIC PIPE FOR FUEL GAS SHALL BE USED ONLY (WHERE)?

OUTSIDE UNDERGROUND

1210.1.7

200

A DEVICE INSTALLED IN A DRAINAGE SYSTEM TO PREVENT REVERSE FLOW IS WHAT?

BACKWATER VALVE

204.0

200

WHAT IS THE CLOSEST YOU CAN INSTALL PEX PIPING TO A WATER HEATER CONNECTION?

18"

604.13

200

THE MINIMUM SIZES FOR VERTICAL AND HORIZONTAL WASTE PIPING SHALL BE DETIRMINED FROM THE?

TOTAL FIXTURE UNITS

703.1

200

EXCEPT FOR ALLYS AND STREETS, HOW FAR SHALL A VENT TERMINATE FROM A LOT LINE?

3'

906.2

200

HORIZONTAL 1/2" STEEL FUEL PIPE SHALL BE SUPPORTED IN INTERVALS NOT TO EXCEED ?

6'

1210.3.5.1

300

LOWEST PORTION OF THE INSIDE OF A HORIZONTAL PIPE IS CALLED THE?

INVERT

211.0

300

WATER VALVES 2 1/2" AND LARGER MAY HAVE BODIES MADE OF?

CAST IRON

606.1

300

WHAT IS AN ACCEPTIABLE FITTING USED TO CONNECT ONE HORIZONTAL WASTE LINE TO ANOTHER HORIZONTAL WASTE LINE?

COMBINATION WYE AND 1/8 BEND

706.3

300

INCREASING ONE PIPE SIZE WILL ALLOW?

REMOVAL OF LENGTH LIMITATIONS

904.2

300

WHAT IS THE MINIMUM SIZE A TRACER WIRE GAUGE SHALL BE?

14 AWG

1210.1.7.2

400

STATIC PRESSURE IS PRESSURE EXISTING WITHOUT ANY FLOW

TRUE

218.0

400

WHAT DOES A WATER SYSTEM WITH A PRESSURE OF 110PSI REQUIRE?

STAINER AND PRESSURE REGULATOR

608.2

400

WHAT IS THE MAXIMUM NUMBER OF FIXTURE UNITS ALLOWED ON A 4" HORIZONTAL DRAIN LINE RAN AT 1/8" PER FOOT OF SLOPE?

173 FIXTURE UNITS

703.2

FOOTNOTE 5

400

COPPER TUBING SHALL NOT BE USED FOR?

CHEMICAL OR INDUSTRIAL WASTES

903.2.2

400

WHAT SHALL A PRESSURE REGULATOR BE PROTECTED AGAINST?

PHYSICAL DAMAGE

1208.8.3

500

A VENT THAT ALSO SERVES AS A DRAIN IS A?

WET VENT

225.0

500

WHEN BRAZING, THE ALLOYS SHALL HAVE A TEMPERATURE ABOVE?

1,000 DEGREES

605.1.1

500

AFTER CAULKING A LEAD JOINT IN A CAST IRON HUB, HOW LOW SHOULD THE FINISHED JOINT BE BELOW THE HUB?

1/8" BELOW

705.2.1

500

PARALLEL VENT STACKS ARE REQUIRED FOR DRAINAGE STACKS THAT EXTEND?

10 STORIES OR MORE

907.1

500

A GAS APPLIANCE REGULATOR SHALL NOT BE VENTED TO THE?

APPLIANCE FLUE OR EXHAUST SYSTEM

1208.8.5