FIRE SUPPRESION SYSTEMS
MISC
GENERAL FIRE
FIRE MONITORING
SAFETY
200

WHAT AREAS ARE SERVED BY THE WET PIPE SYSTEM?

CORRIDORS, FOH/BOH ADMIN, BOTH FLOORS. 

200

ASIDE FROM THE LOW ODOR SMELL, WHAT OTHER INDICATION IS THERE THAT NOVEC 1230 GAS HAS DISPERSED?

VOICE BECOMES DEEPER.

200

WHAT FIRE PANEL REMOTE ANNUNCIATOR WILL THE FIRE DEPARTMENT USE WHEN RESPONDING TO A FIRE

LOBBY 

200

WHAT ARE THE 4 ALARM INDICATIONS FROM OUR FIRE CONTROL PANELS

1. ALARM (FIRE) 

2. SUPERVISORY

3. SECURITY

4. TROUBLE

200

WHAT ARE THE TWO CAL SUITES THAT COT'S WILL UTILIZE 

12 AND 40 CAL

400

WHAT POSITION SHOULD YOU FIND BOTH BYPASS VALVES FOR THE FIRE PUMP?

OPEN

400

 THIS IS A KEYLIGHT DOCUMENT THAT DISPLAYS WHAT INFORMATION

Energized Electrical Work Permit

Decision Tree

400

IN THE CASE OF AN ELECTRICAL FIRE WHAT IS THE IMMEDIATE RESPONSE THAT IS REQUIRED OF THE COT

SECURE POWER TO THE MALFUNCTIONING EQUIPMENT

400

WHEN IT COMES TO THE PODS WHAT DOES FACOPS CHECK FOR SO AS TO PREVENT A FIRE 

OVERHEATING OF THE UPS BATTERIES

400

WHEN SWITCHING A BREAKER FROM ANY POSITION WHY MUST THE COT LOOK AWAY FROM THE BREAKER

BREAKERS ARE UNTESTED, AND IN CASE OF AN ARC FLASH

600

WHAT IS THE PRESSURE THAT THE JOCKEY PUMP NEEDS IN ORDER TO AUTOMATICALLY START?

145 PSI

600

 WHAT IS "LIMITED APPROACH BOUNDARY"  

THE DISTANCE FROM AN EXPOSED ELECTRICAL SOURCE WHERE A SHOCK HAZARD EXISTS

600

WHAT IS THE ROLE OF FACOPS DURING A REAL FIRE/ OR A FIRE DRILL

IDENTIFY THE LOCATION OF THE FIRE, AND ENSURE ALL PERSONNEL ARE OUT OF THE BUILDING

600

AAT THE RIC3 SITE IN THE FACOPS OFFICES 2 DIFFERENT TYPES OF FIRE PANELS ARE USED, WHAT ARE THEY

SIEMENS AND HONEYWELL

600

WHAT DOES A COT NEED TO HAVE PRIOR TO WORKING ON EQUIPMENT OVER 50V

EXEMPTION OR AN ENERGIZED ELECTRICAL WORK PERMIT SIGNED BY EXECUTIVE LEADER FOR THE SITE

800

WHAT DOES THIS PICTURE DISPLAY?

EGRESS ROUTES FOR THE SECOND FLOOR

800

WHEN IS A HOT WORK PERMIT REQUIRED

ANY TYPE OF MAINTENANCE THAT WOULD REQUIRE AN OPEN FLAME, OR A HEAT SOURCE

800

WHAT DOES THIS PICTURE PORTRAY?

OVERALL FIRE PROTECTION PLANS/ZONES

800

WHILE A COT IS DOING ROUNDS WHAT CAN THEY UTILIZE TO IDENTIFY A FIRE OR A RISK OF A FIRE WHILE BEING AWAY FROM AVEVA/IGNITION MONITORING SYSTEM

SIGHT, SMELL, SMOKE, RADIATING HEAT FROM A DOOR, AMBIENT TEMPERATURE 

800

WHEN APPROACHING AN ELECTRICAL COMPONENT, YOU GO THROUGH SEVERAL STEPS TO ENSURE SAFETY WHAT ARE THEY

UTILIZE PPE, USE A HOT-STICK, ARC FLASH BOUNDRIES, LIVE-DEAD-LIVE

1000

UPON THE RECEPTION OF A _________, THE PRE-ACTION SYSTEM ACTUATES VIA A _________ AND PRESSURIZE THE DOWNSTREAM PIPING.

FIRE ALARM.

SOLENOID/VALVE

1000

WHAT CHECKS DO YOU PERFORM PRIOR TO UTILIZING A FIRE EXTRINGUISHER 

SERVICED DATE, PRESSURE IN THE GREEN, PIN NOT BENT AND PRESENT 

1000

LOCATED IN THE BOH WHAT AREAS DO THE HIGHLIGHTED PIPES COVER IN 

1-PA-1-07 : DH 1300 EAST

1-PA-1-06: DH 1200 WEST

1000

YOU ARE A NIGHTSHIFT COT IN THE FACOPS OFFICE, AND YOU HAVE A SECURITY GUARD COME INTO THE OFFICE SOAKING WET INFORMING YOU THAT A SPRINKLER IN THE CUSTOMER CAFETERIA IS SPEWING WATER, WITH NO INDICATION OF AN ACTUAL FIRE. WHAT DO YOU NEED TO DO TO AS THE COT PREVENT FURTHER DAMAGE

VERIFY THAT THERE IS NO ACTUAL FIRE, AND THEN GO TO THE PROPER WET PIPE SYSTEM AND ISOLATE THE PIPE BY SHUTTING THE FLOW OF WATER,AND INFORM LEADERSHIP. START M.I DOCUMENTATION 

1000

WHAT ELECTRICAL TASKS DO NOT REQUIRE AN ENERGIZED ELECTRICAL WORK PERMIT? (NAME TWO)

DIAGNOSTIC TESTING, CIRCUIT IDENTIFICATION, TROUBLESHOOTING, SWITCHES, VISUAL INSPECTION, DC BATTERY CABINET ROUTINE INSPACETIONS AND MAINTENANCE, AND IR SCAN THAT DO NOT ENTER APPROACH BOUNDARY