Multiwire branch circuits shall only supply
What are line to neutral loads
210.4(C)
ENT and associated fittings shall be
What is listed
362.6
Information on the uses permitted for LFMC is found in
What is article 350.10
Receptacle outlets shall be installed so that at no point along the floor line of any wall space is more than
What is 6 feet from a receptacle outlet
210.52(A)(1)
ENT shall not be used
What is in any hazardous location
362.12(1)
The maximum size of LFMC
What is trade size 4
250.12(B)
The rating of any one cord and plug connected utilization equipment not fastened in place shall not exceed
80% of the branch circuit ampere rating
210.23(A)(1)
The maximum size ENT to be used
What is 2 1/2"
362.20(B)
Where equipment grounding is required for type LFNC
What is a separate equipment grounding conductor shall be installed in the conduit
356.60
Where installed in raceways, conductors #8 AWG and larger
What is shall be stranded unless specifically permitted or required elsewhere in this code to be solid
310.3(C)
Outlet boxes or fittings designed for the support of luminaires and lampholders
What is Shall be permitted to support a luminaire or lampholder
314.27(A)
LFNC shall be marked at least every 2 feet, the markings shall include
What is a type designation, and the trade size
356.120
The outer covering of THWN
What is nylon jacket or equivalent
Table 310.4(A)
All joints between lengths of tubing and between tubing and couplings, fittings, and boxes
What is shall be by an approved method
362.48
Type LFNC shall be permitted to be used in
What is exposed or concealed locations
356.10