What are the utility sensing wires on a generac single phase transfer switch
N1&N2
An air cooled unit should run at what rpms
3600
When the cold smart start feature is enabled how long will the generator warm up for before the load is applied
30 seconds
What would be going on with a air cooled unit when you find gray dust in the bottom of the gen by the fan
Generators brushes need replaced
What should you do if you forget to put an item used on your ticket?
Put it on teams in missing parts with customer name and what's missing
What wire grounds itself and transfers the actuator?
Wire 23
What is the minimum allowed compression on a standby air cooled generator motor
150 psi
What is the minimum clearance from openings in walls(operable windows,doors,vents window wells,soffets) that a generac generator can be placed
5ft
What would be the rpm for a 4 pole rotor
1800
What should you do with your ticket when rescheduling a job and who should you let know
Leave your ticket open and let your scheduler know
What wire gives power to wire 23 to allow transfer
Wire 194
What is the maximum allowed gas pressure on air cooled units
11 inw
The Evolution generator is operating in auto,utility voltage is avaliable and the transfer switch has switched over to the generator position. Why is this happening
N1 or N2 fuse is blown (open)
What should be the resistance on the slip rings of a rotor
5-12 ohm
What should you write on the top of your ticket when completing a repair under warranty
*Need to file warranty
What is the proper output voltage on A&B communication wires for kohler units
4 VDC
How do you find top dead center on a 24kw air cooled unit
Use a long wooden stick and roll engine over until piston is topped out on the compression stroke
What is the maximum cooldown for a generac generator?
15 min
What's the voltage need for excitation
Battery voltage
What is the last picture you should take on the generator in watertight?
Controller in auto picture
What does transfer wire warning mean?
Controller is not sensing battery voltage on wires194 or 23
How many feet does each 90 in a pipe run add for a generac generator, what about a kohler generator
Generac- 5 ft
Kohler- 8ft
The generator controller is in auto the unit is running and the transfer switch has transferred to the standby position if wire 23 is shorted to ground when utility service returns what will happen
Nothing
What is all of wire numbers coming from the stator on a generac
1&4 2&3 11s&44s 2&6
When on call what must be done before you go out to a call and what do you do if the install is 6 months or less
Collect 295 and no charge if 6 months or less