SYSTEMS SHALL BE DEEMED THIS AT THE POINT OF PIPELINE INTRUSION.
What is BREACHED
PIPING SHALL BE LABELED BY THESE.
What is STENCILING OR ADHESIVE MARKERS.
THIS ASTM MARKING SHALL BE ON EVERY LENGTH
OF PIPE FOR POSITIVE PRESSURE MEDICAL GAS SYSTEMS.
What is ASTM B 819.
ITS PERMITTED TO HAVE A SINGLE ALARM PANEL IN THESE TWO CATEGORIES.
What is a CATEGORY 2 & CATEGORY 3
CUT ENDS SHALL BE.
What is ROLLED SMOOTH OR DE-BURRED .
DURING THE STANDING PRESSURE TEST THE SOURCE VALVE SHALL BE THIS.
What is CLOSED.
THE PIPING LABEL SHALL INCLUDE THESE THREE THINGS. HINT: ONE IS IF SOMETHING IS NON-STANDARD.
What is the
NAME OR CHEMICAL SYMBOL.
GAS OR VACUUM SYSTEM COLOR CODE
WHERE POSITIVE PRESSURE IS ABOVE NORMAL OPERATING PRESSURE; THE OPERATING PRESSURE IN ADDITION TO THE NAME OF THE GAS.
FIELD INSTALLED MEDICAL-SURGICAL VACUUM AND WAGD. SHALL BE THESE THREE COPPER TUBES.
What is
ASTM B 88
ASTM B 280
ASTM B 819
IN THIS AREA THE ALARMS SENSORS SHALL BE LOCATED ON THE PATIENT OR USE SIDE OF THE ZONE VALVE BOX ASSEMBLY.
What is CRITICAL CARE AREA.
WHILE BRAZING, JOINTS SHALL BE CONTINUOUSLY PURGED WITH THIS GAS.
What is NITROGEN NF.
THE MEDICAL AIR INTAKE SHALL BE LOCATED THIS DISTANCE OFF THE GROUND.
What is 20 FT.
AN OXYGEN LABEL WOULD BE THIS COLOR.
What is GREEN/WHITE OR WHITE/GREEN
(BACKGROUND/TEXT)
FIELD INSTALLED MEDICAL-SURGICAL VACUUM AND WAGD SYSTEMS, IF NOT COPPER, CAN BE THIS MATERIAL.
What is STAINLESS STEEL TUBE.
A HIGH MEDICAL AIR DEW POINT WILL INITIATE A SIGNAL AT THESE TWO ALARM PANELS.
What is LOCAL AND MASTER.
BRAZING ALLOY SHALL EXHIBIT A MELTING TEMPERATURE OF HOW MANY __________*F
What is 1000*F
THE MEDICAL AIR INTAKE SHALL BE LOCATED THIS FAR FROM ANY "NOXIOUS FUMES"
What is 25 FT.
A MEDICAL AIR COLOR LABEL WOULD BE THIS COLOR
What is YELLOW/BLACK
(BACKGROUND/TEXT)
IF JOINED TO THE VACUUM PIPING, WAGD SYSTEM PIPING SHALL BE CONNECTED AT A MINIMUM DISTANCE FROM ANY VACUUM INLET.
What is 5 FT.
ALARM SWITCHES AND SENSORS ARE TO BE INSTALLED TO BE ___________.
What is REMOVABLE.
PIPE LABELS SHALL BE PLACED A MINIMUM DISTANCE APART.
What is 20 FT.
THIS SHALL SEPARATE THE ZONE VALVE BOX ASSEMBLY AND THE OUTLET/INLET THAT IT SERVES.
What is a WALL
What is WHITE/BLACK
(BACKGROUND/TEXT)
ANY POSITIVE PRESSURE MEDICAL GAS SYSTEM OVER 185 PSI SHALL BE ASTM B 819 TYPE ____.
What is K.
5.1.10.1.4*
CANCELABLE AUDIBLE INDICATION OF EACH ALARM CONDITIONS SHALL BE A MINIMUM LEVEL OF ____dBA AT _______FT.
What is 80 dBA at 3 FT.
A VALVE THAT RISES ADJACENT TO THE PIPELINE.
What is a RISER VALVE.