100

Depth of working space in front of a panel shall be a minimum of ____.

36"

110.26(A)(1)

100

There shall not be more than ______ degrees total between pull points of a run of PVC

360

352.26

100

When are cables allowed to support other cables?

Never

300.11(D)

100

The panel circuit directory shall include an approved degree of detail that allows each circuit to be _______________________.

distinguished from all others.

408.4(A)

200

A High-Leg in a three phase delta system must have an outer finish that is _____ in color...

Orange

110.15

200

True or False?

Luminaires are permitted to be installed on trees

True

410.36(G)

200

What is the minimum distance from the bottom of the service disconnect for a mobile home to the finished grade?

2ft

550.32(F)

200

When adjusting ampacity for more than three current carrying conductors in a raceway, what is the adjustment factor for 6 conductors?

80%

310.15(C)(1)

300

NM cable cannot be installed in wet locations. Is it permitted to be in a raceway that is installed outdoors?

NO

300.9

300

Where a cable or raceway is installed through bored holes in joists, the edge of the hole shall not be less than ____ from the nearest edge of the wood.

1.25"

if this cannot be maintained the cable shall  be protected by steel plates

300.4(A)(1)

300

True or False?

EMT is permitted to be used for the support of luminaires

False

358.12(2)

300

In what condition is a raceway required to be sealed?     (duct seal)

when portions of a raceway are subjected to different temperatures

300.7(A)

400

Which is the only orientation that a panelboard is prohibited from being installed in?


Face-up

408.43

400

NEC requires vending machines rated 150v to ground or less, 60a or less, to have what kind of protection?

Class A GFCI protection for personnel

422.5(A)(5)

400

True or False?

LFNC (seal-tight) is permitted to be installed in lengths longer than 6'

True

356.10(5)

400

Outlets supplying all pool motors rated _____amps or less shall be provided with Class A GFCI protection

60

680.21(C)

500

what is the minimum clearance for recessed led luminaires to the nearest point of clothes closet storage space?

6"

410.16(C)(3)

500

Which Code section is this violation illustrating?

230.7

500

When making a splice in a J-box with conductors 4 AWG or larger, the distance between the raceway entry and the opposite wall of the box shall not be less than ____ times the size of the largest raceway in a row.

6

314.28(A)(2)

500

The number of conductors is limited to fill the conduit to what percentage when 2 or more conductors are installed?

40%

Chapter 9, Table 1

352.22

*Note 4 does allow up to 60% fill when the raceway is not longer than 24"